Installation/Operation/Maintenance - Beckett GENISYS 7565 Quick Start Manual

120v advanced burner controls
Table of Contents

Advertisement

Application that is Not Within
the Ratings Listed in This
Section. Improper Control
Operation May Result.
Electrical Ratings
Power:
Voltage: 120 Vac nominal (102 to 132 Vac)
Current: 100 mA nominal (150 mA max at 132 Vac)*
Frequency: 60 Hz
*measured when the motor, valve, and igniter
are all de-energized
Inputs:
Thermostat Anticipator Current: 0.1 A nominal
Thermostat Voltage: 24 Vac nominal
Combustion Air/Blocked Vent
(Front side): 10mA @ 24Vac min
(Underside): 1.9mA @ 120Vac min
Outputs:
Motor: 120 Vac, 10 max full load amps (FLA),
60 max locked rotor amps (LRA)
* Note: Reduce motor FLA rating by igniter and
valve currents
Igniter: 120 Vac, 3 A max
Solenoid Valve: 120 Vac, 1 A max
Environmental Ratings:
Storage and Operating Ambient Temperature:
-40°F to +150°F (-40°C to +65°C)
Moisture: 5 to 95% RH, non-condensing and
non-crystallizing
7585 is rated for condensing environments
Approvals:
Underwriters Laboratory Recognition per UL
60730-1 / 60730-2-5, CSA E60730-1 / C22.2
NO. 60730-2-5
Most codes and standards require additional
safeguards and features for oil burner inputs
above 19.9 gph. Consult the appliance
manufacturer's instructions for control selection.
4
Do Not Use This
Control in an
Do Not Use This Control
Above 19.9 GPH
Installation/Operation/
Maintenance
Incorrect installation or misuse of
this control could result in severe
personal injury, death, or
substantial property damage from
heavy smoke, explosion or fire.
Please read and understand the manual
supplied with this control. This control
must be installed, adjusted and put into
operation only by a qualified individual or
service agency that is:
Licensed or certified to install and provide
technical service to oil heating systems.
Experienced with all applicable codes,
standards and ordinances.
Responsible for the correct installation
and commission of this equipment.
Skilled in the adjustment of oil burners
using combustion test instruments.
The installation must strictly comply with
all applicable codes, authorities having
jurisdiction and the latest revision of
the National Fire Protection Association
Standard for the Installation of Oil-Burning
Equipment, NFPA 31 (or CSA-B139 and
CSA-B140 in Canada).
Regulation by these authorities take
precedence over the general instructions
provided in this installation manual.
If the residence is unattended in severely
cold weather, burner primary control safety
lockout, heating system component failures,
power outages or other electrical system
failures could result in frozen plumbing
and water damage in a matter of hours. For
protection, take preventive actions such
as having a security system installed that
operates during power outages, senses low
temperature and initiates an effective action.
Consult with your heating contractor or a
home security agency.
Professional
Service Required
Frozen Plumbing
and Water
Damage Hazard