fåëí~ää~íáçå
Bolting the flanges of the
busbar housings together
Bolting busbars together
26
Fig. 18: Flange connections with insulating sleeve
ATTENTION!
Sensitive parts of the switchgear may be damaged during installation work at the
busbar and the busbar housings.
!
While working at the busbars or the busbar housings, prop up only on the
supporting frame of the transport unit.
!
Do not prop up on sensitive parts of the switchgear like gas pipes, rupture
diaphragms, shafts, etc.
!
Flange-to-flange connections: Tighten M8x45 bolts crosswise. Tightening torque:
20 Nm.
!
Flange connections with compensator: Push insulating ring between the flanges
(see Fig. 16:, Page 26). Fasten M8x65 bolts crosswise with one insulating sleeve
each. Tightening torque: 20 Nm.
!
Flange connections with insulating joint: Push insulating ring between the
flanges (see Fig. 17:, Page 26). Fasten M8x65 bolts crosswise with one insulating
sleeve each. Tightening torque: 20 Nm.
The busbars are accessed through the horizontal flanges of the busbar housings
(assembly openings).