Fig. 16: Short busbar housing with compensator
Fig. 17: Long busbar housing with insulating joint
!
On the observer's command, push the transport unit to be connected towards the
already mounted one using the lifting gear. The observer checks and corrects the
approach of the busbar sections.
!
Continue approaching the transport units until the flanges touch evenly at the
insulating plates.
!
In case of deviations, correct the position of the transport unit, compensating any
floor unevenness with shims under the corners (same points as for roller pads /
bars).
a
Busbar housing
s
Compensator
d
Insulating ring (thickness: 18 mm)
f
Insulating ring (thickness: 4 mm)
fåëí~ää~íáçå