=USNJVOTPKV=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=oÉîáëáçå=MP
Fig. 5:
Gas pressure indicators at the panel
Fig. 6:
Gas pressure indicators at the panel
DANGER!
Operation with incorrect SF
!
Do not install or put the switchgear into operation with incorrect SF
!
Check the gas pressure in the compartments pre-filled at the factory on the
associated gas pressure indicators. The temperature-dependent limit values must
not be underflown.
!
If the filling pressure is too low: Do not assemble the part of the switchgear
concerned and inform the regional Siemens representative concerned.
-gas pressure can destroy parts of the switchgear.
6
fåëí~ää~íáçå
a
Gas pressure indicators for the bus-
bar compartments (number accor-
ding to the design of the busbar
system)
s
Gas pressure indicator for the cir-
cuit-breaker housing
a
Minimum permissible gas pressure
(signalling contact)
s
Actual gas pressure
d
Maximum permissible gas pres-
sure (signalling contact)
-gas pressures.