Endress+Hauser SmarTec S CLD 132 PROFIBUS-PA Operating Instructions Manual

Endress+Hauser SmarTec S CLD 132 PROFIBUS-PA Operating Instructions Manual

Field communication
Hide thumbs Also See for SmarTec S CLD 132 PROFIBUS-PA:

Advertisement

Quick Links

BA 213C/07/en/11.03
51502194
from software version 1.50
Quality made by
Endress+Hauser
ISO 9001
PROFIBUS-PA/-DP
Field Communication with
SmarTec S CLD 132
Operating Instructions
ENDRESS+HAUSER
ENDRESS+HAUSER
SMARTEC S
SMARTEC S
ALARM
+
CAL
E

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser SmarTec S CLD 132 PROFIBUS-PA

  • Page 1 PROFIBUS-PA/-DP BA 213C/07/en/11.03 51502194 from software version 1.50 Field Communication with SmarTec S CLD 132 Operating Instructions ENDRESS+HAUSER ENDRESS+HAUSER SMARTEC S SMARTEC S ALARM – Quality made by Endress+Hauser ISO 9001...
  • Page 3: Table Of Contents

    Table of contents SmarTec S CLD 132 PROFIBUS-PA/-DP Table of contents Safety instructions ....4 Designated use ......4 Installation, commissioning and operation .
  • Page 4: Safety Instructions

    • Repairs not described in these Operating Instructions may only be carried out directly at the manufacturer’s or by the Endress+Hauser service organisation. Operational safety The transmitter has been designed and tested according to the state of the art and left the factory in perfect functioning order.
  • Page 5: Notes On Safety Conventions And Icons

    SmarTec S CLD 132 PROFIBUS-PA/-DP Safety instructions Notes on safety conventions and icons Warnings Warning! This symbol alerts you to hazards which could cause serious injuries, as well as damage to the instrument, if ignored. Ã Caution! This symbol alerts you to possible faults which could arise from incorrect operation.
  • Page 6: Identification

    • 1 x Operating Instructions for field communication with PROFIBUS BA 213C/07/en • 1 x M12 plug (for device version -PF) If you have any questions, please contact your supplier or your nearest Endress+Hauser sales centre (see the back page of these Operating Instructions). Certificates and approvals Declaration of conformity The transmitter fulfils the statutory requirements of the harmonised European standards.
  • Page 7: Installation

    Note! More detailed information on planning and commissioning a PROFIBUS system can be found in the Operating Instructions BA 198F/00/en. This can be supplied by your nearest Endress+Hauser sales centre (see the back page of these Operating Instructions). ➀ ➁...
  • Page 8: Post-Installation Check

    SmarTec S CLD 132 PROFIBUS-PA/-DP Installation Post-installation check After installing the transmitter, carry out the following checks: Device condition and specifications Note Is the transmitter damaged? Visual inspection Installation Note Are the measuring point number and the labelling Visual inspection...
  • Page 9: Wiring

    SmarTec S CLD 132 PROFIBUS-PA/-DP Wiring Wiring Electrical connection 4.1.1 Opening the housing To open the housing, proceed as follows: Loosen the four Phillips screws and remove the housing cover. Remove the cover frame over the terminal blocks. To do this, guide the screwdriver in accordance with Fig.
  • Page 10 SmarTec S CLD 132 PROFIBUS-PA/-DP Wiring 99 98 95 94 78 85 86 93 94 81 82 99 98 95 94 78 85 86 93 94 81 82 PA– PA– Pg 13.5 C07-CLD132xxx-04-06-00-xx-004 ˆ}° {’Ê BÁÊ–iÛˆ†iÊii†ÌÀˆ†bÊ†œ˜˜i†Ìˆœ˜ 99 98 95 94 78 85 86 93 94 81 82 Pg 13.5...
  • Page 11: Post-Connection Check

    SmarTec S CLD 132 PROFIBUS-PA/-DP Wiring Post-connection check Perform the following checks after completing electrical installation of the measuring device: Device condition and specifications Note Is the measuring device or the cable damaged externally? Visual inspection of profiles Electrical connection...
  • Page 12: Operation

    SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Operation Display and operating elements mS/cm 2000 O213 20 mA ENDRESS+HAUSER SMARTEC S ALARM – C07-CLD132xx-19-06-00-xx-020.eps ˆ}° Ç’Ê E“bÀGi†ÊEÊ)Ê£ÎÓÊÕÃiÀʈ˜ÌiÀvb†i £®ÊˆÃ«bÞÊÃÞ“vœÊvœÀÊb†ÌˆÛiʆœ““Õ˜ˆ†b̈œ˜ÊÛˆbÊBD4 "ÉIEʈ˜ÌiÀvb†i Please refer to the standard Operating Instructions for an explanation of the key assignment and the other icons and symbols.
  • Page 13: Communication

    SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Communication 5.3.1 Block model of PROFIBUS-PA/-DP In the PROFIBUS configuration, all the device parameters are categorised according to their functional properties and tasks and are generally assigned to three different blocks. A block may be regarded as a container in which parameters and the associated functionalities are contained.
  • Page 14 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Physical Block (device block) A Physical Block contains all the data that uniquely identifies and characterises the transmitter. It is an electronic version of a nameplate on the transmitter. Parameters of the Physical Block include the device type, device name, manufacturer ID, serial number, etc.
  • Page 15 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation FACTORY_RESET parameter You can reset the following data via the FACTORY_RESET parameter: 1 all data to PNO default values, 2506 transmitter warm start, 2712 bus address 32768 calibration data, 32769 setting data. Via local operation you can either reset all data to the factory settings or delete the sensor data in menu field S10 (SERVICE function group).
  • Page 16 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Analog Input Block (function block) In the Analog Input function block, the process variables (conductivity and temperature) coming from the Transducer Block are prepared, in terms of instrumentation and control, for the subsequent automation functions, (e.g. scaling and limit value processing).
  • Page 17 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Selecting the operating mode The operating mode is set by means of the MODE_BLK parameter group. The Analog Input function block supports the following operating modes: • AUTO (automatic mode) • MAN (manual mode) •...
  • Page 18 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Simulation of input/output You can simulate the input and output of the function block by means of various parameters of the Analog Input function block: Simulating the input of the Analog Input function block: The SIMULATION parameter group can be used to specify the input value (measured value and status).
  • Page 19 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Transducer Analog Input Function Block Block °C PV_SCALE OUT_SCALE tempe- rature ENDRESS+HAUSER ENDRESS+HAUSER SMARTEC S SMARTEC S ALARM – 25 °C 77 °F °F –10 ... 150 °C C07-CLD132xx-02-06-00-en-007.eps ˆ}° £ä’Ê E†bˆ˜}ÊÌ…iʈ˜«ÕÌÊÛbÕiÊvœÀÊÌ…iÊÁ˜bœ}Ê"˜«ÕÌÊvÕ˜†Ìˆœ˜Êvœ†Ž Limit values You can set two warning limits and two alarm limits for monitoring your process.
  • Page 20 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation 5.3.2 Cyclic data exchange Cyclic data exchange is used to transfer the measured values during operation. Module for the cyclic data telegram The SmarTec S CLD 132 makes the following modules available as input data (data from transmitter to PLC) for the cyclic data telegram (see also block model in Fig.
  • Page 21 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation IEEE-754 floating point number: Byte n Byte n+1 Byte n+2 Byte n+3 Bit 7 Bit 6 Bit 0 Bit 7 Bit 6 Bit 0 Bit 7 Bit 0 Bit 7 Bit 0 −1 −2 −3...
  • Page 22 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Status codes for the OUT parameter of the Analog Input block Status code Device status Meaning Limits 0x00 non-specific 0x01 LOW_LIM 0x02 HIGH_LIM 0x03 CONST 0x04 configuration error 0x05 LOW_LIM 0x06 HIGH_LIM 0x07 CONST...
  • Page 23 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Status code Device status Meaning Limits 0x89 GOOD active advisory alarm LOW_LIM 0x8A HIGH_LIM 0x8D GOOD active critical alarm LOW_LIM 0x8E HIGH_LIM 5.3.3 Configuration Device Master Files The device is ready for system integration once commissioning has been effected via the local display or the Class 2 master (Commuwin II).
  • Page 24 Each device is assigned an identification number (ID No.) by the Profibus User Organisation (PNO). The name of the Device Master File is derived from this. For Endress+Hauser, this ID No. starts with the manufacturer ID 15xx. In order to ensure clarity, the GSD names at Endress+Hauser are as follows:...
  • Page 25 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation  • “Info” folder: Information relating to the transmitter and any dependencies in the device software. Note! • Please read the information in the "Info" folder carefully before configuring. Working with GSD files The GSDs must be integrated into the automation system. Depending on the software that is being used, the GSD files can be copied to the program-specific directory or can be read into the database using the import function within the configuration software.
  • Page 26 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Ê Configuration examples with Simatic HW-Konfig SmarTec S CLD 132 full configuration using the manufacturer-specific GSD file Byte Byte Data blocks Status Access length length Block description Extended (Input) (Output) block code 0 ... 4 –...
  • Page 27 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation SmarTec S CLD 132 partial configuration using the manufacturer-specific GSD file Byte Byte Data blocks Status Access length length Block description Extended (Input) (Output) block code 0 ... 4 – Analog Input active read...
  • Page 28 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation SmarTec S CLD 132 partial configuration using the manufacturer-specific GSD file Replacing measured variables with free places. Byte Byte Data blocks Status Access length length Block description Extended (Input) (Output) block code 0 ... 4 –...
  • Page 29 A Class 2 master can access the blocks that are shown in the illustration. The parameters, which can be operated in the Endress+Hauser operating program Commuwin II, are displayed in the form of a matrix on Page 38.
  • Page 30 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Slot/index tables The device parameters are listed in the following tables. You can access these parameters by means of the slot and index number. The individual blocks each comprise standard parameters, block parameters and manufacturer-specific parameters to an extent.
  • Page 31 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Parameter Slot Index Size Type Acc. Store matrix (bytes) (CW II) FACTORY_RESET Unsigned16 r, w 0x8000: Reset calibration data 0x8001: Reset setting data 0x0001: PNO defaults All data 2506: warm-start 2712: reset bus addr.
  • Page 32 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Analyser Transducer Block There are two Analyser Transducer Blocks in the SmarTec S. These are distributed to slots 1 and 2 in the following order: Main measured value (Main Process Value) Temperature measured value (Temperature)
  • Page 33 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Analog Input block There are two Analog Input Blocks in the SmarTec S transmitter. These are distributed to slots 1 and 2 in the following order: Main measured value (Main Process Value) Temperature measured value (Temperature)
  • Page 34 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Manufacturer-specific parameters SmarTec S CLD 132 (Commuwin II matrix) Parameter Slot Index Size Type Acc. Store matrix (bytes) (CW II) Measured value V0H0 Float Temperature V0H1 Float Operating mode V0H2 Unsigned8 0: Conductivity 1: Concentration...
  • Page 35 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Parameter Slot Index Size Type Acc. Store matrix (bytes) (CW II) Material selection of processed V4H4 Unsigned8 r, w measuring range 0: NaOH 1: H2SO4 2: H3PO4 3: HNO3 4: User 1... Temperature compensation...
  • Page 36 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Parameter Slot Index Size Type Acc. Store matrix (bytes) (CW II) PCS Alarm V7H0 Unsigned8 r, w 0: no PCS 1: 1 hour 2: 2 hours 3: 4 hours Relay contact type V8H1 Unsigned8...
  • Page 37 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation 5.3.5 Operation using Commuwin II You can access the block parameters by means of a PROFIBUS-DP Class 2 master such as Commuwin II. Commuwin II is a graphic operating program with various communication protocols. Commuwin II runs on an IBM-compatible PC or laptop. The computer must be equipped with a PROFIBUS interface, i.e.
  • Page 38 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Device menu You can use the “Device” menu to choose between operation via the matrix or via the graphic interface. • In the case of matrix operation, the device or profile parameters are loaded in a matrix.
  • Page 39 SmarTec S CLD 132 PROFIBUS-PA/-DP Operation Inductive XX.xx mS/cm 292.37 mS/cm 280.10 mS/cm 25.1 °C V0 SETUP 1 OPERATING MODE MEASURING UNIT DECIMALS MEASURING UNIT SIGNAL DAMPING RAW VALUE ACT. MRS MEASURED VALU TEMPERATURE Pt 100 5.900 1/cm 1.000 25.1 °C 0.0 °C...
  • Page 40: Commissioning

    SmarTec S CLD 132 PROFIBUS-PA/-DP Commissioning Commissioning à Function check Caution! • Before power-up, check all the connections again for correctness. • Also ensure that the post-connection check (Chap. 4.2) has been performed. Warning! • Before power-up, make sure there is no danger to the measuring point. Uncontrolled actuated pumps, valves or similar could lead to damage to instruments.
  • Page 41 SmarTec S CLD 132 PROFIBUS-PA/-DP Commissioning  6.2.1 Setting the device address via the operating menu Note! You can only set the address via the software if DIL switch 8 is set to the software position. On leaving the factory, switch 8 is already set to software as shown in Fig. 15 (information on the DIL switch is provided in Section 6.2.3).
  • Page 42 SmarTec S CLD 132 PROFIBUS-PA/-DP Commissioning 6.2.3 Setting the device address via DIL switch (hardware setting) Please proceed as follows to set the device address: Loosen the four Phillips screws and remove the housing cover. The DIL switch is situated on the electronic module above the display.
  • Page 43: Maintenance

    SmarTec S CLD 132 PROFIBUS-PA/-DP Maintenance Maintenance For maintenance at the measuring point, please consult the standard Operating Instructions BA 207C/07/en. Endress+Hauser...
  • Page 44: Accessories

    SmarTec S CLD 132 PROFIBUS-PA/-DP Accessories Accessories ➀ ➁ ➄ ENDRESS+HAUSER ENDRESS+HAUSER SMARTEC S SMARTEC S ALARM ALARM ➂ – PROFIBUS-DP ➅ ENDRESS+HAUSER ENDRESS+HAUSER SMARTEC S SMARTEC S ALARM – ➃ ➄ ENDRESS+HAUSER ENDRESS+HAUSER SMARTEC S SMARTEC S ALARM –...
  • Page 45 Cable, prepared, yellow, 10 m 52001042 Device Master File (GSD file) The GSDs for all Endress+Hauser devices can be acquired via: • Internet (E+H): http://www.endress.com Products / Process Solutions / PROFIBUS / GSD files • Internet (PNO): http://www.profibus.com, GSD library •...
  • Page 46: Troubleshooting

    SmarTec S CLD 132 PROFIBUS-PA/-DP Troubleshooting Troubleshooting System error messages DIAGNOSIS and DIAGNOSIS_EXTENSION parameters The DIAGNOSIS and DIAGNOSIS_EXTENSION parameters are generated from the device-specific errors. SmarTec S CLD 132 PROFIBUS diagnosis NAMUR Error Description DIAGNOSIS DIAGNOSIS_ Measured value status class...
  • Page 47 SmarTec S CLD 132 PROFIBUS-PA/-DP Troubleshooting NAMUR Error Description DIAGNOSIS DIAGNOSIS_ Measured value status class EXTENSION Quality Sub-status Funct. E101 Service function active – – check Funct. E102 Manual operation active check Funct. E106 Download active 00 00 00 80 - EXTENSION_AVAILABLE 00 00 00 00 00 80 -...
  • Page 48: Technical Data

    SmarTec S CLD 132 PROFIBUS-PA/-DP Technical data Technical data 10.1 Output PROFIBUS-PA Output signal PROFIBUS-PA: EN 50170 vol. 2, Profile version 3.0 PA function Slave Transmission rate 31.25 kBit/s Signal coding Manchester II Response time slave Approx. 20 ms Signal on alarm Status and alarm messages in accordance with PROFIBUS-PA, Profile Version 3.0...
  • Page 49: Human Interface

    SmarTec S CLD 132 PROFIBUS-PA/-DP Technical data 10.3 Human interface Local operation Via keyboard Bus address Set via • DIL switch or • Operating menu or • Set_Slave_Adr service Communication interface PROFIBUS-PA/-DP 10.4 Standards and guidelines PROFIBUS EN 50170, vol. 2 PROFIBUS-DP EN 50170, vol.
  • Page 50: Index

    Index SmarTec S CLD 132 PROFIBUS-PA/-DP Index Installation ....... . 4 Installation check .
  • Page 51 Declaration of contamination Dear customer, Because of legal determinations and for the safety of our employes and operating equipment we need this “Declaration of contamination” with your signature before your order can be handled. Please put the completely filled in declaration to the instrument and to the shipping documents in any case. Add also safety sheets and/or specific handling instructions if necessary.
  • Page 52 Poland – Wroclaw Costa Rica – San Jose ❑ Sakura Endress Co. Ltd. ❑ Endress+Hauser Polska Sp. z o.o. Tel. (01) 88 05 60, Fax (01) 88 05 63 35 Euro-Tec S.A. Tel. (0422) 54 06 11, Fax (0422) 55 02 75 Tel.

This manual is also suitable for:

Smartec s cld 132 profibus-dpProfibus-paProfibus-dp

Table of Contents