To Connect The Safety Thermostat (Normally Closed Contact); To Connect A Smart Grid - Daikin Altherma 3 R W Installation Manual

Hide thumbs Also See for Altherma 3 R W:
Table of Contents

Advertisement

A
A
B
C
B
C
a
Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
6.3.10
To connect the safety thermostat
(normally closed contact)
Wires: 2×0.75 mm²
Maximum length: 50 m
Safety thermostat contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free contact shall ensure the
minimum applicable load of 15 V DC, 10 mA.
1 Open the following (see
"4.2.1 To open the indoor
1 Front panel
2 Switch box cover
3 Switch box
2 Connect the safety thermostat (normally closed) cable to the
appropriate terminals as shown in the illustration below.
Note: The jumper wire (factory-mounted) must be removed from the
respective terminals.
EBBH/X11+16DF
Daikin Altherma 3 R W
4P643600-1B – 2021.10
1 2
3
4 5
A8P
X801M
1
3 2
5 4
unit" [ 4  13]):
3
2
1
A
B
C
B
a
3 Fix the cable with cable ties to the cable tie mountings.
NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, we recommend the following:
▪ The safety thermostat is automatically resettable.
▪ The safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ There is a minimum distance of 2 m between the safety
thermostat and the motorized 3‑way valve delivered
with the domestic hot water tank.
NOTICE
Error. If you remove the jumper (open circuit) but do NOT
connect the safety thermostat, stop error 8H-03 will occur.
6.3.11

To connect a Smart Grid

This topic describes 2 possible ways to connect the indoor unit to a
Smart Grid:
▪ In case of low voltage Smart Grid contacts
▪ In case of high voltage Smart Grid contacts. This requires the
installation of the Smart Grid relay kit (EKRELSG).
The 2 incoming Smart Grid contacts can activate the following Smart
Grid modes:
Smart Grid contact
1
0
6 Electrical installation
A
14
13
Q4L
C
Smart Grid operation mode
2
Free running
0
Installation manual
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents