Overview of electrical connections
Plug sYS
Terminals
Function
212.1
Cooling control
AC
AC function (active cooling)
212.2
Heating circuit pump for
heating circuit without mixer
A1
(A1/HC1)
212.3
DHW circulation pump
Installation sequence
(cont.)
Explanation
Connection values
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Circuit on site, see separate "connection
and wiring diagram" sheet 201 to
sheet 204
■ This pump is connected in addition to
the secondary pump if a heating water
buffer cylinder is installed.
■ Connect temperature controller as a
maximum temperature limiter for un-
derfloor heating circuit (if installed) in
series (see following chapter)
Connection values
■ Output: 100 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
On-site connection, see separate "con-
nection and wiring diagram" sheet 120.
Use contactor, if required; see separate
"connection and wiring diagram"
sheet 121, sheet 122.
Connection values
■ Output: 50 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
On-site connection, see separate "con-
nection and wiring diagram" sheet 150.
Use contactor, if required; see separate
"connection and wiring diagram"
sheet 151, sheet 152.
59