Specification Type Ww 301.A125 To Ww 302.A300 - Viessmann VITOCAL 300-G PRO Installation And Service Instructions Manual

Table of Contents

Advertisement

Specification

Specification type WW 301.A125 to WW 302.A300

Operation: water/water
Type WW
Output data to EN 14511
(W10/W35, 5 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of perform-
ance ε (COP)
Water (primary cir-
cuit)
Content
Nominal flow rate to
EN 14511
Min. flow rate (4 K
spread)
Pressure drop (at
nominal flow rate)
Max. flow tempera-
ture
Min. flow temperature °C
Heating water (sec-
ondary circuit)
Content
Nominal flow rate to
EN 14511
Min. flow rate (10 K
spread)
Pressure drop (at min.
flow rate)
Flow temperature at
min. primary circuit
flow temperature 8 °C
146
1-stage 301
A125 A155 A125 A155 A200 A250
kW
116
160 112.1 145.1
kW
103
120
kW
20.9
24.6
5.74
5.79
l
111
111
m³/h
29.2
34.5
m³/h
21.9
25.8
mbar
310
465
°C
20
8
l
22.7
28.7
m³/h
20.0
24.1
m³/h
11.0
12.5
mbar
100
100
°C
60
2-stage 302
94.2 121.6
18.3
24.4
6.1
5.94
111
111
27.1
35.0
20.3
26.4
285
459
20
20
20
8
8
8
22.7
28.7
19.3
24.9
10.0
12.5
90
100
60
65
65
A300
190
240
290
159
199
244
32.1
42.1
49.5
5.92
5.70
5.86
293
293
293
45.6
57.1
70.0
33.1
42.5
52.9
342
623
937
20
20
8
8
38.7
53.5
57.1
32.7
41.3
49.9
16.4
20.7
25.0
100
100
100
60
60
20
8
60