Siting
(cont.)
!
Please note
Observe the permissible floor
load.
Total weight type
BW 301.A090 to BW 302.A250:
BW 301.A090 740 kg
BW 301.A120 840 kg
BW 302.A090 745 kg
BW 302.A120 850 kg
BW 302.A150 1190 kg
BW 302.A180 1260 kg
BW 302.A250 1375 kg
Total weight type
WW 301.A125 to
WW 302.A300:
WW 301.A125 1040 kg
WW 301.A155 1050 kg
WW 302.A125 1075 kg
WW 302.A155 1085 kg
WW 302.A200 1360 kg
WW 302.A250 1405 kg
WW 302.A300 1445 kg
■ To prevent the transmission of struc-
ture-borne noise, never site the appli-
ance on ceilings with wooden joists
(e.g. in the attic).
■ Level the appliance.
Where uneven floors are compensa-
ted, distribute the load on the adjusta-
ble feet evenly.
Preparing for installation
■ Observe minimum room volume (to
EN 378).
Note
Additional country-specific regulations
also apply.
Minimum room volume type
BW 301.A090 to BW 302.A250:
BW 301.A090 54 m
BW 301.A120 68 m
BW 302.A090 53 m
BW 302.A120 68 m
BW 302.A150 86 m
BW 302.A180 103 m
BW 302.A250 141 m
Minimum room volume type
WW 301.A125 to WW 302.A300:
WW 301.A125 42 m
WW 301.A155 49 m
WW 302.A125 42 m
WW 302.A155 49 m
WW 302.A200 59 m
WW 302.A250 65 m
WW 302.A300 73 m
■ Observe the required floor area and
minimum clearances (see the follow-
ing chapter).
3
3
3
3
3
3
3
3
3
3
3
3
3
3