Viessmann VITOCAL 300-G PRO Installation And Service Instructions Manual page 143

Table of Contents

Advertisement

Specification type BW 301.A090 to BW 302.A250
Operation: water/water with intermediate circuit
Type BW
Output data to EN 14511
(W10/W35, 5 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of perform-
ance ε (COP)
Brine (intermediate cir-
cuit –5 °C)
Content
Min. flow rate (5 K
spread)
Pressure drop (at min.
flow rate)
Max. flow temperature
Min. flow temperature
Heating water (secon-
dary circuit)
Content
Min. flow rate (10 K
spread)
Pressure drop (at min.
flow rate)
Max. flow temperature
Note
■ Output data to EN 14511 correspond
to a temperature spread of 3 K at a
brine inlet temperature of 0 °C and
brine outlet of –3 °C.
■ The specified flow rates are rounded
up or down.
■ Operation as water/water heat pump
with intermediate circuit:
If the brine temperature of the inter-
mediate circuit is reduced to 8 °C from
10 °C, the heat pump output is
reduced by approx. 5 %
1-stage 301
A090 A120 A090
kW
125
152 118.8
kW
104.5
128
kW
21
25.6
5.95
5.93
l
33.0
42.0
m³/h
26.0
31.0
mbar
175
175
°C
20
20
°C
7
7
l
22.7
28.7
m³/
10.8
13.1
h
mba
130
130
r
°C
60
60
Information on refrigerant
The EC safety datasheet for R410A can
be obtained from the Technical Services
department of Viessmann Werke.
(cont.)
2-stage 302
A120 A150 A180
153.0
198
101
129.0
168
18.9
25.3
32.1
6.2
6.05
6.10
33.0
42.0
55.2
24.9
31.8
41.0
170
170
195
20
20
20
7
7
7
22.7
28.7
38.7
10.3
13.2
17.1
130
130
130
65
65
60
Specification
A250
235
302
197
252
41
51.8
5.73
5.83
69.0
89.4
48.0
62.0
210
280
20
20
7
7
53.5
57.1
20.5
26.0
130
160
60
60
143