Viessmann VITOCROSSAL Service Instructions Manual page 69

Single boiler: 80 to 318 kw. twin boiler: 240 to 636 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

Fault codes
(cont.)
Fault code dis-
System characteristics
played
48
Mixer is being closed.
4C
Mixer is being closed.
50
No DHW heating
58
No DHW heating
90
Control mode
91
Control mode
92
No solar DHW heating
93
Control mode
94
No solar DHW heating
98
Control mode
99
Control mode
9A
No solar DHW heating
9B
Control mode
9C
No solar DHW heating
9E
Control mode
9F
Control mode
A3
Burner blocked.
A4
Control mode
A7
Control mode as per deliv-
ered condition
B0
Burner blocked
Cause
Lead break, flow tempera-
ture sensor, heating circuit
2 (with mixer)
Lead break, flow tempera-
ture sensor, heating circuit
3 (with mixer)
Short circuit, cylinder tem-
perature sensor
Lead break, cylinder tem-
perature sensor
Short circuit, temperature
sensor
/
Short circuit, temperature
sensor
Short circuit, collector
temperature sensor
Short circuit, cylinder tem-
perature sensor
Short circuit, cylinder tem-
perature sensor
Lead break, temperature
sensor
/
Lead break, temperature
sensor
Lead break, collector tem-
perature sensor
Lead break, cylinder tem-
perature sensor
Lead break, cylinder tem-
perature sensor
No or inadequate flow rate
in collector circuit, or tem-
perature limiter has re-
sponded.
Solar control module or
Vitosolic fault
Flue gas temperature sen-
sor incorrectly positioned.
Max. system pressure ex-
ceeded
Programming unit faulty
Short circuit, flue gas tem-
perature sensor
Troubleshooting
Measures
Check flow temperature sensor.
Check flow temperature sensor.
Check sensors (see page 76).
Check sensors (see page 76).
Check sensor
on solar control
/
module.
Check sensor
on solar control
module.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check temperature sensor at ter-
minal S3 on the Vitosolic 100.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check sensor
/
on solar control
module.
Check sensor
on solar control
module.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check temperature sensor at ter-
minal S3 on the Vitosolic 100.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check solar circuit pump and solar
circuit. Acknowledge fault mes-
sage.
Replace solar control module or Vi-
tosolic.
Fit flue gas temperature sensor
correctly. See page 77
Check system pressure: Max.
3 bar (0.3 MPa)
Check the function and sizing of
the diaphragm expansion vessel.
Vent the heating system.
Replace the programming unit.
Check flue gas temperature sen-
sor.
on
&
%
on
on
&
on
%
69