Viessmann VITOCROSSAL Service Instructions Manual page 43

Single boiler: 80 to 318 kw. twin boiler: 240 to 636 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Party mode time limit
F2:8
Time limit for party mode or exter-
nal operating program changeover
via pushbutton: 8 h (only for
weather-compensated control
units)
*1
Pump control in "Only DHW"
F6:25
In "Only DHW" mode, the heating
circuit pump is constantly on (only
for constant temperature control
units)
Pump control in "Standby mode"
F7:25
In "Standby mode", the heating cir-
cuit pump is constantly on (only for
constant temperature control units)
Start temperature raising
F8:-5
Temperature limit for terminating
reduced mode -5 °C.
Observe setting for coding address
"A3". (only for weather-compensa-
ted control units)
End temperature raising
F9:-14
Temperature limit for raising the re-
duced set room temperature
-14
C. (only for weather-compen-
º
sated control units)
Set flow temperature increase
FA:20
Increasing the set boiler water
temperature or set flow tempera-
ture by 20 % when changing from
operation with reduced room tem-
perature to operation with standard
room temperature (only for weath-
er-compensated control units).
Duration set flow temperature increase
FB:60
Duration for increasing the set boil-
er water or flow temperature (see
coding address "FA") 60 min (only
for weather-compensated control
units).
In the "Heating and DHW" program, party mode ends automatically when the system changes over to operation at stand-
*1
ard room temperature.
(cont.)
Possible change
F2:0
No time limit for party mode
F2:1
Time limit adjustable from 1 to 12 h
to
F2:12
F6:0
In "Only DHW" mode, the heating
circuit pump is permanently off.
F6:1
In "Only DHW" mode, the heating
to
circuit pump is started 1 to 24 times
F6:24
per day for 10 min each time.
F7:0
In "Standby mode", the heating cir-
cuit pump is constantly off
F7:1
In "Standby mode", the heating cir-
to
cuit pump is started 1 to 24 times
F7:24
per day for 10 min each time.
F8:+10
Temperature limit adjustable from
to
+10 to -60 °C
F8:-60
F8:-61
Function disabled
F9:+10
Temperature limit for raising the set
to
room temperature to the value se-
F9:-60
lected for standard mode adjustable
from
+10 to -60 °C
FA:0
Temperature rise adjustable from 0
to
to 50 %
FA:50
FB:0
Duration adjustable from 0 to
to
240 min
FB:240
Code 1
*1
*1
43