Viessmann VITOCROSSAL Service Instructions Manual page 37

Single boiler: 80 to 318 kw. twin boiler: 240 to 636 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

General/Group "1"
(cont.)
Value, ad-
Description
dress 00: ...
2
1 heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automatical-
ly)
3
1 heating circuit with mixer M2 (heating circuit 2), without DHW heating
4
1 heating circuit with mixer M2 (heating circuit 2), with DHW heating
5
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), without DHW heating (code is set automatically)
6
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), with DHW heating (code is set automatically)
7
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), without DHW heating
8
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), with DHW heating
9
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), without DHW heating (code is set
automatically)
10
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), with DHW heating (code is set au-
tomatically)
System examples
Coding in the delivered condition
Code 1
77:1
LON subscriber number, if LON
communication module is installed
Detached house/apartment building
7F:1
Detached house
Lock out controls
8F:0
Operation enabled in standard
menu and extended menu.
Note
The relevant code is only enabled
when you exit the service menu.
Possible change
77:2
LON subscriber number, adjustable
to
from 1 to 99:
77:99
1 - 4 = Boiler
5 - 9 = Do not adjust
10 - 90 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only once.
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
8F:1
Operation is blocked in standard
menu and extended menu. Emis-
sions test mode can be activated.
8F:2
Operation is enabled in standard
menu, but blocked in extended
menu. Emissions test mode can be
activated.
Code 1
37