Viessmann VITOCROSSAL Service Instructions Manual page 53

Single boiler: 80 to 318 kw. twin boiler: 240 to 636 kw. gas condensing boiler with matrix cylinder burner. open flue and room sealed operation
Table of Contents

Advertisement

Solar/Group "4"
(cont.)
Coding in the delivered condition
07:0
Interval function of solar circuit
pump switched off
08:60
The solar circuit pump is stopped if
the actual cylinder temperature
reaches 60 °C (maximum cylinder
temperature).
09:130
The solar circuit pump is stopped if
the collector temperature reaches
130 °C (maximum collector tem-
perature to protect the system
components)
0A:5
To protect the system components
and heat transfer medium, the
speed of the solar circuit pump is
reduced if the differential between
the actual cylinder temperature
and the set cylinder temperature is
less than 5 K.
0B:0
Collector frost protection function
switched off
0C:1
Delta T monitoring switched on
No flow rate detected in the collec-
tor circuit or flow rate too low.
0D:1
Night-time DHW circulation moni-
toring switched on
Unintentional flow rate in the col-
lector circuit is captured (e.g. at
night).
0E:1
Calculation of solar yield with
Viessmann heat transfer medium
0F:70
The flow rate in the collector circuit
at the maximum pump speed is set
to 7 l/min.
10:0
Target temperature control switch-
ed off (see coding address 11)
Possible change
07:1
Interval function of solar circuit pump
switched on
To capture the collector temperature
more accurately, the solar circuit
pump periodically starts for a short
duration.
08:10
The maximum cylinder temperature
to
is adjustable from 10 to 90 °C.
08:90
09:20
The temperature is adjustable from
to
20 to 200 °C.
09:200
0A:0
The differential between the set cyl-
to
inder temperature and the start point
0A:40
for reducing the stagnation time is
adjustable from 0 to 40 K.
0B:1
Collector frost protection function
switched on (not required with
Viessmann heat transfer medium).
0C:0
Delta T monitoring switched off
0D:0
Night-time DHW circulation monitor-
ing switched off
0E:2
Calculation of solar yield with water
as heat transfer medium (do not se-
lect as operation is only possible
with Viessmann heat transfer medi-
um)
0E:0
Calculation of solar yield switched
off
0F:1
Flow rate in the collector circuit ad-
to
justable from 0.1 to 25.5 l/min
0F:255
10:1
Target temperature control switched
on
Code 2
53