Condition Monitoring Indication; Test Modes; Function Test; Control Test - ABB RE 54 Operator's Manual

Feeder, machine and transformer terminals
Table of Contents

Advertisement

1MRS750500-MUM
6.3.3.
6.4.
6.4.1.
6.4.2.
Feeder, Machine and Transformer Terminals
Operator's Manual
In addition, the fault indication text has been replaced by a more informative text,
that will also show the IRF code.
I n t e r n a l f a u l t
I R F c o d e 4 0 6

Condition monitoring indication

If the terminal includes condition monitoring functions that are not directly related
to any protection functions of the terminal or to the internal condition of the
terminal, they are indicated in the assisting window by the message SUPERV and
an explanatory text, see the example below.
C M T C S 1 : S U P E R V
T r i p c i r c u i t s u p

Test modes

There are various test modes for each of the following four categories:
• Function
• Control
• MIMIC
• I/O test
• IRF test

Function test

The outputs of a function block can be activated locally via the HMI or externally
via serial communication. The outputs are activated by using control parameters of
the function.
For further details of functions, refer to the CD-ROM Technical Descriptions of
Functions (1MRS750889-MCD).

Control test

The system provides a general interlocking bypass mode (parameter "Interl bypass"
in MAIN MENU/Control/General) that overrides all interlocking signals.
Activation of the interlocking bypass mode activates the interlocking enable signals
of all control objects. Thus, all control actions are possible, and the enable signals of
controllable objects are not checked while the objects are commanded. As long as
the mode is active, the Interlocking LED indicator on the HMI is red and flashing.
Additionally, the assisting window of the MIMIC view will indicate the special
condition.
RE_ 54_
irf_fi_b
assisupi_b
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref 54 seriesRem 54 series

Table of Contents