1MRS750500-MUM
5.3.4.
5.4.
Feeder, Machine and Transformer Terminals
Operator's Manual
ALARM view
The ALARM view shows all the configured alarms with alarm texts. Active (not
acknowledged) control alarms are distinguished from non-active alarms by LED
indicators and user-defined alarm texts.
CB spring ready
SF6 gas density
Temperature
Interlocking
C c l e a r s a l a r m s
E V E N T
M I M I C
Fig. 5.3.4.-1
ALARM view
Technical level
The interactive communication between the user and the HMI at technical level is
based on menus that contain information for programming the terminal.
• To enter the MAIN MENU at technical level, press [E] for 2 s in the MIMIC view
at user level and enter the password if required
• To return to the user level, press [E] for 1 s in the MAIN MENU
Changing level
Fig. 5.4.-1 Moving between user level and technical level
[C] button functions in the ALARM view
• If there are active indications, press [C]
for 2 s to reset
• When there are no active indications,
press [C] for 2 s to acknowledge alarms
• The acknowledgement proceeds
according to the configuration
MIMIC view
CB OK
Note ! Password 3
can be used, if
wanted, when
entering the Main
menu (see chapter
5.2)
MAINMENU
Status
Main menu
Protection
Control
Cond. monit.
Measurement
Communication
General func.
Tests
Information
Configuration
RE_ 54_
21 kV
AROFF
User level
2 s
1 s
Technical level
alarmvie_b
levelcha_b
23