Technical data

12 Technical data
Specifications subject to change without notice.
Values at nominal conditions.
12.1 Sunny Boy 8000TL-US
PV generator connection data
Maximum DC power
Maximum array input power (DC@STC)
Maximum DC voltage
Peak power track voltage
Maximum DC input current
Number of MPP-Trackers
Grid connection data
Nominal AC power
Maximum AC power
Reduced power output at 140 °F (60 °C)
Maximum AC current
Nominal AC voltage
Nominal AC voltage range
Nominal AC frequency
Nominal AC frequency range
Power factor
Current THD
AC connection/power balancing
Ground fault monitoring (R-Iso)
Protection Devices
DC reverse polarity protection
AC short circuit protection
AC overcurrent protection
Grid monitoring (SMA Grid Guard
60
SB8-10TL-IUS103811
®
 2)
SMA America, LLC
8,300 W
10,000 W
600 V
300 V ... 480 V
28 A
1 (OptiTrac)
8,000 W
8,000 W
8,000 W
40 A
208 V
183 V ... 229 V
60 Hz
59.3 HZ ... 60.5 Hz
1 at Nominal Power
< 4 %
Dual Phase/O
yes
yes, short circuit diode
yes, software controlled
yes, current controlled
yes