NOTE: Reference the PWRcell Battery Installation and
Owner's Manual for advanced battery settings.

Adjusting Inverter Settings

1. See
Table
6-1. Navigate to the inverter device
page using the right arrow key (next page right of
the home screen).
2. Push the center button.
3. Select Mod. Settings using the down arrow to scroll
and the center button to select.
Setpoint
PLM_Channel
TargMaxImprtP
-30,000 to +30,000 Watts
TargMinImprtP
-30,000 to +30,000 Watts
EnaIslanding
EnaExtTransfer
ExtTransVolt
50 – 200 Volts
GridGoodTime
1 – 360 Seconds
Export Override
PLM_Disable
CalOverride
CTTurnsRatio
1,500 – 3,000 Turns
EnaLoadShed
EnaACdump
GridParInvrtrs
Installation and Owner's Manual for Generac PWRCell Inverter
Table 6-1. Adjusting Inverter Settings
Range
Default
0 – 12
1
0
0
on / off
on
on / off
off
95
15
on / off
off
on / off
off
on / off
off
1,500
0,1,2
0
on / off
off
1 – 2
1
4. Scroll through the settings using the up / down
arrow keys.
5. Use the center button to select a setting.
6. Use the up / down arrow keys to change the value
of a setting.
7. Use the center button to deselect a setting.
8. Scroll down and save all changes before exiting
the Mod. Settings menu.
9. Select Mod. Settings again to verify changes were
saved.
Channel for REbus communications. All devices in a system must use
the same channel (except REbus Beacon). Do not set equipment to
channel 0 unless performing
Maximum Threshold for importing power before the battery will dis-
charge in Self Supply Mode to offset.
Minimum power import maintained by charging the battery from the grid
in Self Supply Mode.
Allows system to island, providing backup power during a grid outage.
Turn on if an external automatic transfer switch (ATS) has been installed
to operate with the Inverter.
Minimum voltage from the utility that must be present for the inverter to
reconnect back to the grid.
Length of time required for the inverter to reconnect to the utility upon
sensing grid voltage return.
Formerly called Zero Export, this setting will inhibit the PWRcell system
from exporting power to the grid. This setting is for temporary use and
will not satisfy CRD200 Import Only Compliance. See
Override (optional)
This setting will disable the power line communications coming from the
Overrides inverter logic for automatic detection of included Generac cur-
rent transformers (CTs).
Allows a different turns ratio to be set for specific CTs.
Select 1 if using SMM devices to shed loads. Select 2 if using the PWR-
cell ATS Controller to shed loads (with or without SMMs).
When available this setting will shed AC coupled PV where necessary.
This setting allows for two inverters to share one set of CTs. Set to 2 if
daisy chaining CTs between two inverters.
Commissioning
Description
Commissioning Multiple Inverter
Systems
.
Set Export
.
inverter.