Siemens POS8.4420/109 Basic Documentation page 23

Room operator units
Hide thumbs Also See for POS8.4420/109:
Table of Contents

Advertisement

Building Automation Device
BA-Model
Binary Calculated Value
Present-Value
Active
Update-Count
PL-1:PR=DHWSM.
I/O-Address
DHWPushUser;
APP=DHW.1;
represent
PL-Link Data Acquisition
PL-Link Room Unit
User DHW Settings UDHWSET
LTE IR (Auto)
DHWModeUserEff
DHWModeUserLocked
LTE W (false)
LTE IR (false)
DHWPushActive
Management Data
Configuration Data
DHW Zone
A6V11471220_en--_e
Control Program
Multistate-Calculated-Value
Present-Value
Number-of-States
State-Text
Reduced
Off/FrostProtect
LegioProtect
n
Update-Count
PL-1:PR=DHWSM.
I/O-Address
DHWModeUser;
APP=DHW.1;
represent
DHW Setpoint Manager DHWSM
LTE IR (Auto)
DHWModeUser
DHWPushUser
LTE IR (Trigger)
Configuration Data
DHW Zone
PrioThreshDHWModeUserLocked
PrioDirectControl
DHWZone 1
DHWModeUser
LTE IR (Auto)
DHWPushUser
LTE IR (Trigger)
1
Parameters required to realize the full function:
Property
Property
name
identifier
Interface
1
Object Type
DHWModeEff
DHWSM.51
local copy *)
BuildingZone
101
Room
102
Subzone
103
Multistate-Process-Value
Auto
Present-Value
5
Priority-Array
Auto
Present-Priority
Normal
Number-of-States
Why-Indication [16]
State-Text
Off/FrostProtect
n
Update-Count
PL-1:PR=DHWSM.
I/O-Address
DHWModeEff;
APP=DHW.1;
represent
DHWZone 1
DHWModeUserEff
DHWModeUserLocked
DHWModeEff
DHWModeEffWhy
DHWPushActive
1
7
8
LTE IR (Normal)
LTE IR (...)
Device Configuration
Data TxtCatalog
- ...
- Equipm Protect
- ...
- Manual Control
- Scheduler
- ...
Property
LTE service
access
R
---
----
IR.ind
213
R
R/W
---
R/W
---
R/W
---
Engineering
Binary Process Value
Normal
Present-Value
....
Priority-Array
16
Present-Priority
4
x
Normal
Reduced
LegioProtect
n
Update-Count
PL-1:PR=DHWSM.
I/O-Address
DHWPushActive;
APP=DHW.1;
represent
LTE IR (Auto)
LTE W (false)
optional output:
„Why" value may
LTE IR (Normal)
be derived from BA
Present-Priority or
LTE IR (...)
Why-Indication
LTE IR (false)
User HVAC Display UHD
DHWZone 1
DHWModeEff
DHWModeEffWhy
Management Data
Configuration Data
DHW Zone
1
TxtRefDHWModeEffWhy
TxtRef [1..n]
Description
390 = UHD
Process Data
Input
---
Configuration
Data
Configuration
Data
Configuration
Data
5
Inactive
....
16
n
optional input
KNX
Datapoint
Type (DPT)
DPT_PropData
Type (DPT_ID
= 7.010)
DPT_DHWMod
e_Z
Diagnostic
Value
DPT_UCountV
alue8_Z
DPT_UCountV
alue8_Z
DPT_UCountV
alue8_Z
23 | 70