Siemens POS8.4420/109 Basic Documentation page 19

Room operator units
Hide thumbs Also See for POS8.4420/109:
Table of Contents

Advertisement

Temporary mode
Building Automation Device
Room Control Room 1
BA-Model
Binary-Calc-Value ResetTmpFanRequest
Binary-Calc-Value KitchenHoodRequest
Binary-Calc-Value FirePlaceRequest
Binary-Calc-Value FanBoostRequest
Present-Value
Active
Update-Count
PL-1:PR=FSSM.
I/O-Address
FanBoostReq;
GEO=24.6.1;
represent
PL-Link Data Acquisition
[cASA-4.2-100-N]
new optional FSSM
input process signals
for temporary HRV fan
operation
PL-Link RU-B Room Unit
User FanSpeed Settings UFS
RoomGroup 24.6.1
FanSpeedUserEff
LTE IR (Auto)
FanSpeedUserLocked
LTE W (false)
FanSpeedUserMinIN
FanSpeedUserMaxIN
Management Data
UFS Discovery & Diagnostic Data
UFS Configuration Data
A6V11471220_en--_e
Analog-Calc-Value ManualFanSpeed
Binary-Calc-Value ManualFanMode
n
Analog-Proc-Value FanSpeedEff
represent
Fan Speed Setpoint Manager FSSM
Room Group 24.6.1
FanSpeedUser
LTE IR (Auto)
{
LTE IR (Trigger)
FanBoostReq
LTE IR (Trigger)
FirePlaceReq
LTE IR (Trigger)
KitchenHoodReq
LTE IR (Trigger)
ResetTmpFanReq
Config-Property-Client
FSSM Configuration Data
Geographical Zone
PrioThreshFanSpeedUserLocked
PrioDirectControl
FanSpeedUser
LTE IR (Auto)
FanBoostReq
LTE IR (Trigger)
FirePlaceReq
LTE IR (Trigger)
KitchenHoodReq
LTE IR (Trigger)
ResetTmpFanReq
LTE IR (Trigger)
[cASA-4.2-100-N]
new optional UFS
output process signals
for temporary HRV fan
operation
Parameters required to realize the full function:
Analog-Proc-Value TemporaryFanRemainTime
Present-Value
I/O-Address
represent
represent
LTE IR (33.3%)
FanSpeedEff
FanSpeedUserEff
LTE IR (Auto)
FanSpeedUserLocked
LTE W (false)
LTE IR (8)
FanSpeedEffWhy
LTE W (0%)
FanSpeedUserMinIN
LTE W (100%)
FanSpeedUserMaxIN
TmpFanModeRemainTime
LTE IR (15min)
TmpFanMode
LTE IR (FirePlace)
NumberOfSteps
Property_W (3)
24.6.1
7
8
}
{
LTE IR (FirePlace)
[cASA-4.2-100-N]
new optional UHD
input process signals
for temporary HRV fan
operation
[cASA-4.2-100-N]
parameters to enable/
disable operation of
temporary fan modes
at runtime
Engineering
Multistate-Proc-Value TemporaryFanMode
15 min
Present-Value
State-Text
PL-1:PR=FSSM.
TmpFanMode
RemainTime;
I/O-Address
GEO=24.6.1;
represent
}
[cASA-4.2-100-N]
new optional FSSM
output process signals
for temporary HRV fan
operation
User HVAC Display UHD
RoomGroup 24.6.1
LTE IR (33.3%)
FanSpeedEff
LTE IR (...)
FanSpeedEffWhy
LTE IR (15min)
TmpFanModeRemainTime
TmpFanMode
Management Data
UHD Discovery & Diagnostic Data
UFS Configuration Data
RU Device Object
Configuration Data
EnableFanBoostOp
EnableFirePlaceOp
EnableKitchenHoodOp
5
FirePlaceMode
None
FanBoostMode
FirePlaceMode
KitchenHoodMode
PL-1:PR=FSSM.
TmpFanMode;
GEO=24.6.1;
true
true
true
19 | 70

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pos8.4440/109

Table of Contents