Hanging unit
Balance the unit weight center for
safety before unit hanging. Refer to
Table 1 and Figure 2 for unit gross
weight and mass distribution.
Warning
Field hanging device must
have a safety factor to bear unit weight.
Under capability hanging device
used will cause body hurt or death of
personnel and damage to the unit.
Table 1 Unit Gross Weight
Unit Model
Unit Gross Weight
009
012
015
018
024
030
036
042
048
060
Note data tolerance ±15%.
Horizontal unit installation
clearance
Adequate clearance should be spared
for service access. Required service
access for horizontal unit is shown in
Figure 3. A 457mm pass-way space
should be reserved around the unit
for service. For units with supply and
return at the same side, as shown in
Figure 3, a 76mm pass-way at one
side of the unit, other methods should
be taken for thermal expansion valve
maintenance. This configuration
is typical for units installed in a
constrained place, corridor specially.
Ve r t i c a l u n i t i n s t a l l a t i o n
clearance
Adequate clearance around the unit

Preinstallation

must be reserved for convenient
service and fluent ventilation. Minimum
clearance required for vertical unit
service and ventilation is shown in
Figure 4.
70kg
75kg
95kg
98kg
107kg
127kg
140kg
148kg
157kg
163kg
FACTORY MOLINTED
HANGING DEVICE
THERMAL EXPANSION
DRAIN LINE
Figure 2 Unit Mass Distribution
18" (457)
(4-SIDES)
LEFT RETURN
BACK SUPPLY
UNIT FAONT
18" (457)
(4-SIDES)
RIGHT RETURN
RIGHT RETURN
BACK SUPPLY
UNIT FAONT
Figure 3 Horizontal Unit Service Clearance
24"
UN I T FRON T
( 6 10 )
1"
( 2 5 . 4
)
RIGHT RETURN
TOP/BACK SUPPLY
Figure 4 Vertical Unit Service Clearance
5
WATER-IN/OUT
VALVE
COMPRESSOR
A-WAY
VALVE
LEFT RETURN-AIR
ARRANGEMENT
18" (457)
18" (457)
(4-SIDES)
(3-SIDES)
LEFT RETURN
LEFT RETURN
RIGHT SUPPLY
LEFT SUPPLY
UNIT FAONT
UNIT FAONT
18" (457)
18" (457)
(3-SIDES)
(4-SIDES)
RIGHT RETURN
RIGHT SUPPLY
LEFT SUPPLY
3"
(76)
UNIT FAONT
UNIT FAONT
UN I T
FRONT
1"
( 2 5 . 4
)
UNIT
FRONT
TO T'STAT
OR SENSOR
3"
(76)
24"
( 6 10)
LEFT RETURN
TOP/BACK SUPPL