Troubleshooting - Trane Axiom GEHB Installation Operation & Maintenance

Water-source heat pump
Table of Contents

Advertisement

Problem
Heating Cooling Cause
No response to
X
any thermostat
X
setting
X
X
Unit short
X
X
cycles
X
B l o w e r r u n s
X
but compressor
X
does not
X
X
X
X
X
X
Insufficient ca-
X
pacity
X
X
X
X
X
X
X
X
X
X
X
X
High pressure
switch open
X
X
X
X
H i g h h e a d
pressure
X
X
X
X
X
L o w s u c t i o n
X
pressure
X

Troubleshooting

X
Main power off
X
Defective control transformer
X
Broken or loose connection
X
Defective thermostat
X
Thermostat improperly located
X
Defective compressor overload
X
Heat anticipator setting
X
Defective compressor overload
X
Defective compressor contactor
X
Defective lockout relay
X
Supply voltage too low
X
Defective compressor capacitor
X
Defective windings
X
Limit switches open
X
Seized compressor
X
Dirty filter
X
Blower RPM too low
X
(1-phase)blower running backward
X
Loss of conditioned air due to leaks in ductwork
X
Introduction of excessively hot return air
X
Introduction of excessively low return air
X
Low on refrigerant charge
X
Cap/tube strainer or expansion valve is restricted Replace
X
Defective reversing valve
X
Thermostat improperly located
X
Unit undersized
X
Inadequate water flow
X
Scaling in chiller
X
Water too hot
Water too cold
X
Inadequate GPM
X
Water too hot
Inadequate air flow
Dirty filter
X
Overcharged with refrigerant
X
Defective pressure switch
X
Trash in chiller
X
Low water flow
X
Overcharged with refrigerant
X
Non-condensibles in system
X
Water too hot
Dirty filter
Inadequate air flow
X
Undercharged
X
Restricted metering device
X
Inadequate air flow
X
Dirty filter
21
Correction
Check fuses
Replace
Repair
Replace
Relocate
Replace
Adjust
Replace(if external)
Replace
Replace
Correct
Replace
Replace
Check cause/Replace
"Bump off" with start capacitor/replace
Replace/clean
Correct
Checking wiring at capacitor
Repair leaks
Correct
Correct
Locate leak, repair and recharge
See Touch Test Chart
Relocate
Recalculate heat gains/losses
Increase GPM
Clean or replace
Decrease temperature
Increase temperature
Increase
Decrease temperature
Check, clean blower and coil
Clean/replace
Decrease charge
Check replace
Backflush
Increase GPM
Decrease charge
Evacuate and recharge
Decrease temperature
Clean/replace
Check, clean blower and coil
Locate leak, repair and recharge
Repair/replace
Check, clean blower and coil
Clean/replace