Page 1
Installation, Operation, and Maintenance Water Source Heat Pump Axiom™ Water-to-Water — EXW 5 to 20 Tons — 60 Hz SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
Page 2
CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs. Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For...
Page 3
WARNING This document and the information in it are the property of Personal Protective Equipment (PPE) Trane, and may not be used or reproduced in whole or in Required! part without written permission. Trane reserves the right to revise this publication at any time, and to make changes Failure to wear proper PPE for the job being undertaken could result in death or serious injury.
General Information located internal to the cabinet on the 5-ton through 20- ton equipment. WARNING • After assuring that charge has been retained, reinstall Fiberglass Wool! the caps to assure that refrigerant leakage does not Exposition to glass wool fibers without all necessary occur.
Page 6
Deluxe 24V Controls The Deluxe 24V control design will incorporate a microprocessor-based control board. The Trane microprocessor board is factory wired to a terminal strip to provide all necessary terminals for field connection. The...
Dimensions and Clearances WARNING Improper Unit Lift! Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point.
Page 9
Dimensions and Clearances Figure 2. EXW*060 SOURCE SIDE HEAT EXCHANGER LOAD SIDE HEAT EXCHANGER [17] [508] CONTROL BOX [1016] ISO VIEW TOP VIEW CONTROL BOX ACCESS HIGH VOLTAGE Ø1 1/8 [28.6] [559] 24 VOLT Ø7/8 [22.2] 10 1/8 [257] 4 1/8 [105] 2 3/8 [25]...
Page 10
Dimensions and Clearances Figure 3. EXW*120 SOURCE SIDE HEAT EXCHANGER WATER OUT WATER OUT LOAD SIDE HEAT EXCHANGER WATER IN WATER IN [50.8] [50.8] [25.4] [25.4] [838.2] CONTROL BOX [1473.1] ISO VIEW TOP VIEW CONTROL BOX ACCESS 24 VOLT Ø7/8 [22.2] [610] HIGH VOLTAGE Ø1 1/8 [28.6]...
Page 11
Dimensions and Clearances Figure 4. EXW*240 SOURCE SIDE LOAD SIDE HEAT EXCHANGER HEAT EXCHANGER 3 1/8 [78.0] 1 1/4 [30.4] 31 3/8 [797.0] CONTROL BOX 81 1/2 [2069.9] ISO VIEW TOP VIEW CONTROL BOX ACCESS HIGH VOLTAGE Ø1 1/8 [28.6] 24 VOLT [762.0] 21 3/4...
Installation General Installation Checks WARNING The checklist below is a summary of the steps required to Improper Unit Lift! successfully install a unit. This checklist is intended to acquaint the installing personnel with procedures Failure to properly lift unit in a LEVEL position could required in the installation process.
Installation Figure 5. Water connection Cleaning and Flushing the Water Loop water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 After the piping system is complete, the flexible hose hours. connectors should be doubled back to complete the water 6.
Installation Using Antifreeze Field Installed Power Wiring In areas of the country where entering water temperatures drop below 45°F or where piping is being run through WARNING areas subject to freezing, the loop must be freeze Hazardous Voltage! protected by using an approved antifreeze solution to prevent the earth loop water from freezing inside the heat Failure to disconnect power before servicing could exchanger.
Installation Controls Using 24 Vac Figure 7. Unit power wiring Before installing any wire, refer to the electrical access UNIT POWER WIRING locations on the unit dimensions on Dimensions and 3 PHASE POWER SUPPLY Clearances chapter. 1TB1 • Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three --------------------- --------------- L3...
Electrical Table 6. Electrical performance EXW* units Maximum Minimum Maximum Minimum Overcurrent VOLTS-AC/ Utilization Utilization Total Unit Comp Comp No. of Circuit Protective Model No. HZ/PH Voltage Voltage RLA (ea) LRA (ea) Compres. Ampacity Device 208/60/1 26.3 26.3 134.0 32.88 230/60/1 26.3 26.3...
Pre-Start Pre-Start-up Checklist Before energizing the unit, the following system devices must be checked: – Is the high voltage power supply correct and in accordance with the nameplate ratings? – Is the field wiring and circuit protection the correct size? –...
Unit Start-up Start-up with the system controls is included below: 1. Set the system control to the cooling mode of operation. 2. Turn on the circulation pumps. The compressor should NOT run. 3. Reduce the temperature control setting until the compressor, reversing valve and solenoid valve are energized.
Operating Data Table 13. Water volume Unit Size Water Volume Cubic Inches Water Volume Cubic Feet Water Volume Gallons (U.S) EXW*060 359.6 0.21 1.57 EXW*120 719.2 0.42 3.14 EXW*240 2079.0 1.20 8.98 Note: The above water volume is the total unit water volume ( Source + Load), divide the above volume by 2 to obtain source or load side volumes individually. Flow Checks For the operating temperature drop (heating) and rise (cooling), refer to Table 7 through Table 12 for the proper...
Maintenance Preventive Maintenance It should be noted that the water quality should be checked periodically. Refer to the table below. Maintenance on the unit is simplified with the following Table 14. Water quality table preventive suggestions: Scaling WARNING Calcium and magnesium (total hardness) Less than 350 ppm Hazardous Voltage! Corrosion Failure to disconnect power before servicing could...
Troubleshooting • Verify that the unit is receiving electric supply power. WARNING • Ensure that the fuses in the fused disconnect (field installed) are intact. Hazardous Service Procedures! After completing the preliminary checks, inspect the unit Failure to follow all precautions in this manual and on for other obvious problems such as leaking connection, the tags, stickers, and labels could result in death or broken or disconnected wires, etc.
Page 28
Troubleshooting Table 15. Troubleshooting checklist (continued) Problem Heating Cooling Cause Correction Trash in heat exchanger Backflush Low water flow Increase GPM High head pressure Overcharge of refrigerant Decrease charge Non-condensable in system Evacuate and recharge by weight Water too hot Decrease temperature Undercharged Locate leak, repair and recharge...
INPUT. TERMINAL 1TB2-7 AND 1TB2-8 AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOLID LINES INDICATE WIRING BY THE TRANE CO. ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE WHEN CONTROL 1U1 AND 1U2 GOES INTO MANUAL LOCKOUT MODE. NUMBERS ALONG THE LEFT SIDE OF THE CONTACTS RATED FOR CLASS 2 24V.
Page 30
INPUT. TERMINAL 1TB2-7 AND 1TB2-8 AND/OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD. SOLID LINES INDICATE WIRING BY THE TRANE CO. ISOLATED GENERAL ALARM CONTACTS. CONTACTS CLOSE WHEN CONTROL 1U1 AND 1U2 GOES INTO MANUAL LOCKOUT MODE. NUMBERS ALONG THE LEFT SIDE OF THE CONTACTS RATED FOR CLASS 2 24V.
The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard 1- year coverage through the fifth year. These extended warranties apply only to new equipment installed in domestic Trane sales territories and must be ordered prior to start-up. WSHP-SVX02E-EN...
Page 32
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.