Free Cooling Status Menu – FCOOL_ST (continued)
No.
Point name
6
fc_fanst
7
fc_fansp
8
FC_HOUR
9
FC_FAN1S
10
FC_FAN1H
11
FC_FAN2S
12
FC_FAN2H
13
FC_FAN3S
14
FC_FAN3H
15
FC_FAN4S
16
FC_FAN4H
17
FC_FAN5S
18
FC_FAN5H
19
FC_FAN6S
20
FC_FAN6H
21
FC_FAN7S
22
FC_FAN7H
*Depends on the selected language (English by default).
Modes Menu – MODES
No.
Point name
1
m_delay
2
m_2ndspt
3
m_reset
4
m_limit
5
m_ramp
6
m_cooler
7
m_clpmpp
8
m_cdpmpp
9
m_night
10
m_SM
11
m_leadla
12
m_heater
13
m_lo_ewt
14
m_boiler
15
m_ice
16
m_sst_a
17
m_sst_b
18
m_dgt_a
19
m_dgt_b
20
m_hp_a
21
m_hp_b
22
m_sh_a
23
m_sh_b
24
m_dhw
25
m_summer
*Depends on the selected language (English by default).
20
Status
Unit
0 to 10
-
0 to 100
%
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
0 to 999999
-
0 to 999999
hour
Status
Unit
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
no / yes
-
Displayed text*
FC Fan Stage
FC Varifan Speed
FC Operating Hours
FC Fan Stage 1 Start
FC Fan Stage 1 Hours
FC Fan Stage 2 Start
FC Fan Stage 2 Hours
FC Fan Stage 3 Start
FC Fan Stage 3 Hours
FC Fan Stage 4 Start
FC Fan Stage 4 Hours
FC Fan Stage 5 Start
FC Fan Stage 5 Hours
FC Fan Stage 6 Start
FC Fan Stage 6 Hours
FC Fan Stage 7 Start
FC Fan Stage 7 Hours
Displayed text*
Delay Active
Second Setpoint Active
Reset Active
Demand Limit Active
Ramp Loading Active
Cooler Heater Active
Cooler Pump Per. Active
Cond. Pump Per. Active
Night Low Noise Active
System Manager Active
Master Slave Active
Electric Heat Active
Heating Low EWT lockout
Boiler Active
Ice Mode Active
Low Suction Circuit A
Low Suction Circuit B
High DGT Circuit A
High DGT Circuit B
High Pres Override cir A
High Pres Override cir B
Low SuperHeat circuit A
Low SuperHeat circuit B
Domestic Hot Water Mode
Summer Mode Active
Description
Free Cooling / Dry Cooler fan stage
Free Cooling / Dry Cooler: Fan speed
Free Cooling / Dry cooler: Operating hours
FC / Fan stage 1: Number of starts
FC / Fan stage 1: Operating hours
FC / Fan stage 2: Number of starts
FC / Fan stage 2: Operating hours
FC / Fan stage 3: Number of starts
FC / Fan stage 3: Operating hours
FC / Fan stage 4: Number of starts
FC / Fan stage 4: Operating hours
FC / Fan stage 5: Number of starts
FC / Fan stage 5: Operating hours
FC / Fan stage 6: Number of starts
FC / Fan stage 6: Operating hours
FC / Fan stage 7: Number of starts
FC / Fan stage 7: Operating hours
Description
Start-up delay in effect
Second setpoint in use: The setpoint used during
unoccupied periods
Setpoint reset active
Demand limit active
Ramp loading active
Pump enabled for freeze protection
Evaporator pump active periodically
Condenser pump active periodically
Night low noise active
System Manager active
Master/slave mode active
Electric heating active
Heating low EWT lockout
Boiler active status
Ice mode active (cooling setpoint 3 is used)
Low suction, circuit A
Low suction, circuit B
High DGT, circuit A
High DGT, circuit B
High pressure override, circuit A
High pressure override, circuit B
Low superheat, circuit A
Low superheat, circuit B
Domestic hot water mode status
Summer mode status