Carrier 30WG Operation Instructions Manual page 17

Touch pilot junior control
Table of Contents

Advertisement

Setpoint Menu – SETPOINT
No.
Point name
Status
1
csp1
-28.9 to 20.0
2
csp2
-28.9 to 20.0
3
ice_sp
-28.9 to 20.0
4
hsp1
20.0 to 65.0
5
hsp2
20.0 to 65.0
6
hsp3
20.0 to 65.0
7
ramp_sp
0.1 to 1.1
8
lim_sp1
0 to 100
9
lim_sp2
0 to 100
10
lim_sp3
0 to 100
11
cond_sp
30.0 to 58.0
*Depends on the selected language (English by default).
Inputs Menu – INPUTS
No.
Point name
1
ONOFF_SW
2
HC_SW
3
on_ctrl
4
SETP_SW1
5
SETP_SW2
6
LIM_SW1
7
LIM_SW2
8
FLOW_SW
9
DIFF_FLW
10
LOCK_SW
11
DSHTR_SW
12
HP_SW_A
13
HP_SW_B
14
SP_RESET
*Depends on the selected language (English by default).
Outputs Menu – OUTPUTS
No.
Point name
1
CP_A1
2
CP_A2
3
CP_A3
4
FAN_A
5
EXVPosA
6
HD_POS_A
7
RV_A
8
LLS_A
9
CP_B1
10
CP_B2
11
FAN_B
12
EXVPosB
13
HD_POS_B
14
RV_B
Default
Unit
12.0
°C
12.0
°C
12.0
°C
50.0
°C
50.0
°C
50.0
°C
0.6
^C
100
%
100
%
100
%
40.0
°C
Status
Unit
open / close
-
open / close
-
off / cool / heat
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
open / close
-
0 to 20
mA
Status
Unit
off / on
-
off / on
-
off / on
-
-
%
%
off / on
-
off / on
-
off / on
-
off / on
-
-
%
%
off / on
-
Displayed text*
Cooling Setpoint 1
Cooling Setpoint 2
Cooling Ice Setpoint
Heating Setpoint 1
Heating Setpoint 2
Heating Setpoint 3
Ramp Loading Setpoint Ramp loading setpoint (rate at which the water
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Condensing Setpoint
Displayed text*
On/Off - Remote Switch
Remote heat/Cool Switch
Current Control
Remote Setpoint Switch1
Remote Setpoint Switch2
Limit Switch 1 Status
Limit Switch 2 Status
Exchanger Flow Switch
Diff Exchanger Flow Sw
Lock Input
Desuper heater demand
High Pressure Switch A
High Pressure Switch B
Setpoint Reset Signal
Displayed text*
Compressor A1 Output
Compressor A2 Output
Compressor A3 Output
Condenser Fan Stages A
EXV Position Circuit A
Head Pressure position A
Reverse Valve cir A
Liquid Line Solenoid A
Compressor B1 Output
Compressor B2 Output
Condenser Fan Stages B
EXV Position Circuit B
Head Pressure position B
Reverse Valve cir B
Description
Cooling setpoint 1 (used during occupied periods)
Cooling setpoint 2 (used during unoccupied periods)
Cooling ice setpoint
Heating setpoint 1 (used during occupied periods)
Heating setpoint 2 (used during unoccupied periods)
Used as Domestic Hot Water Setpoint when Heating
Device Control is selected (optional)
temperature may change within one minute)
Demand limit setpoint 1
Demand limit setpoint 2
Demand limit setpoint 3
Condensing setpoint (see also section 8.12.3)
Description
Remote on/off switch
Remote heating/cooling selection switch
Current control: Off, Cool, Heat
Remote Setpoint Switch 1
Remote Setpoint Switch 2
Demand limit switch 1
Not applicable (please ignore this parameter)
Flow switch status
Condenser Flow switch status (currently not available)
Customer interlock status
Desuperheater demand (currently not available)
High pressure switch A
High pressure switch B
Setpoint reset signal
Description
Compressor A1 command
Compressor A2 command
Compressor A3 command
Condenser fan stages, circuit A
EXV position, circuit A
Head pressure, circuit A
Not applicable (please ignore this parameter)
Liquid line solenoid valve status, circuit A
Compressor B1 command
Compressor B2 command
Condenser fan stages, circuit B
EXV position, circuit B
Head pressure, circuit B
Not applicable (please ignore this parameter)
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

30wga61wg