Carrier 30WG Operation Instructions Manual page 16

Touch pilot junior control
Table of Contents

Advertisement

General Parameters Menu – GENUNIT (continued)
No.
Point name
10
CHIL_S_S
11
CHIL_OCC
12
CAP_T
13
CAPA_T
14
CAPB_T
15
DEM_LIM
16
SP
17
CTRL_PNT
18
EMSTOP
*Depends on the selected language (English by default).
Temperature Menu – TEMP
No.
Point name
1
EWT
2
LWT
3
SST_A
4
SST_B
5
SUCT_A
6
SUCT_B
7
OAT
8
COND_EWT
9
COND_LWT
10
SCT_A
11
SCT_B
12
DGT_A
13
DGT_B
14
CHWSTEMP
15
HTWSTEMP
16
DRY_LWT
17
SPACETMP
*Depends on the selected language (English by default).
Pressure Menu – PRESSURE
No.
Point name
1
DP_A
2
SP_A
3
DP_B
4
SP_B
*Depends on the selected language (English by default).
16
Status
Unit
dsable / enable
-
no / yes
-
0 to 100
%
0 to 100
%
0 to 100
%
0 to 100
%
-
°C
-20.0 to 67.2
°C
dsable / enable
-
Status
Unit
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
-
°C
Status
Unit
-
kPa
-
kPa
-
kPa
-
kPa
Displayed text*
Net.: Cmd Start/Stop
Net.: Cmd Occupied
Percent Total Capacity
Circuit A Total Capacity
Circuit B Total Capacity
Active Demand Limit Val
Current Setpoint
Control Point
Emergency Stop
Displayed text*
Entering Water Temp
Leaving Water Temp
Saturated Suction Tp A
Saturated Suction Tp B
Gas Suction Temp A
Gas Suction Temp B
Outside Air Temperature
Cond Entering Water Temp
Cond Leaving Water Temp
Saturated Condens Tp A
Saturated Condens Tp B
Discharge Gas Temp cir A
Discharge Gas Temp cir B
Chilled Water Syst Temp
Heat Water Syst Temp
Dry Cooler Leaving WT
Optional Space Temp
Displayed text*
Discharge Pressure A
Suction Pressure A
Discharge Pressure B
Suction Pressure B
Description
Unit start/stop via Network: When the unit is in
Network mode, start/stop command can be forced
Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
Total unit capacity
Total capacity, circuit A
Total capacity, circuit B
Active demand limit value: When the unit is in Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
Current setpoint
Control point: Water temperature that the unit must
produce
Emergency stop: Used to stop the unit regardless of
its active operating type
Description
Evaporator entering water temperature: Used for
capacity control
Evaporator leaving water temperature: Used for
capacity control
Saturated suction temperature, circuit A
Saturated suction temperature, circuit B
Compressor suction temperature, circuit A
Compressor suction temperature, circuit B
Outdoor air temperature: Used to determine a number
of control mechanisms
Condenser entering water temperature
Condenser leaving water temperature
Saturated condensing temperature, circuit A
Saturated condensing temperature, circuit B
Discharge gas temperature, circuit A
Discharge gas temperature, circuit B
Chilled water system temperature (used for master/
slave assembly control when cooling )
Hot water system temperature (used for master/slave
assembly control when heating)
Dry cooler – leaving water temperature
Outdoor air temperature reading
(optional OAT sensor needed)
Description
Compressor discharge pressure, circuit A
Compressor suction pressure, circuit A
Compressor discharge pressure, circuit B
Compressor suction pressure, circuit B