Omron NXEIP202 User Manual page 331

Machine automation controller
Table of Contents

Advertisement

Event name
NX Bus Cycle Delay Detected
Meaning
Exceeding the NX bus cycle was detected.
Source
EtherNet/IP
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The NX bus cycle was exceeded.
Attached
None
information
Precautions/
None
Remarks
Event name
NTP Client Setting Error
Meaning
An error was detected in the NTP client settings
Source
EtherNet/IP
Error
Level
attributes
Effects
User program
Sys-
Variable
tem-defined
None
variables
Cause and
Assumed cause
correction
The IP address set in the NTP cli-
ent settings is invalid.
Power was interrupted when a
download was in progress for the
NTP client settings.
Attached
None
information
Precautions/
None
Remarks
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Use the Support Software and
download the configuration infor-
mation.
Source details
Observation
Recovery
Continues.
Operation
Data type
---
Correction
Correct the IP address of the NTP
server in the NTP client settings
and then download it again. Then,
cycle the power supply to the Eth-
erNet/IP Coupler Unit or restart
the EtherNet/IP Coupler Unit.
Download the NTP client settings
again. Then, cycle the power sup-
ply to the EtherNet/IP Coupler
Unit or restart the EtherNet/IP
Coupler Unit.
12 Troubleshooting
Event code
350E0000 hex
EtherNet/IP
Detection
Coupler Unit
timing
---
Log category
Not affected.
Name
---
Prevention
None
Event code
35510000 hex
EtherNet/IP
Detection
Coupler Unit
timing
Cycle power to
Log category
the EtherNet/IP
Coupler Unit or
restart the
Slave Terminal.
Time cannot be acquired from NTP.
Name
---
Prevention
Set the IP address of the BOOTP
server correctly in the NTP client
settings.
Do not turn OFF the power supply
while a download is in progress for
the NTP client settings.
Safe-Opera-
tional or Opera-
tional state
System
12
When power is
turned ON to
the EtherNet/IP
Coupler Unit or
the Slave Ter-
minal is
restarted
System
12 - 43