Omron NXEIP202 User Manual page 308

Machine automation controller
Table of Contents

Advertisement

12 Troubleshooting
Connection status
General
Additional
Status
Status
(hex)
(hex)
01
031C
Error code generated by originator:
Some other error occurred.
08
---
Error code returned from target:
There is no Forward Open or Large
Forward Open service in the target
device.
D0
0001
Error code generated by originator:
The connection operation is
stopped.
D0
0002
Error code generated by originator:
The connection is being opened
(opening processing in progress).
OMRON error code
01
0810
Error code returned from target:
New data could not be obtained from
the CPU Unit when opening connec-
tion. (The Unit will automatically
recover, and attempt to open the
connection again.)
01
0811
Error code generated by originator:
New data could not be obtained from
the CPU Unit when opening connec-
tion. (The Unit will automatically
recover, and attempt to open the
connection again.)
Additional Information
For details, refer to the CS and CJ Series EtherNet/IP Units Operation Manual (Cat. No.
W465), the user's manual for the built-in EtherNet/IP port of the connected CPU Unit or Indus-
trial PC, or the manual for the connected EtherNet/IP master from another company.
12 - 20
Source of error
This error does not occur.
This error does not occur.
The connection was stopped
because the Tag Data Link Stop
Bit was turned ON, or the set-
tings data is being downloaded.
Either turn ON the Tag Data Link
Start Switch, or wait until the set-
tings data has been downloaded.
This code includes fatal Control-
ler errors and Unit failure. To han-
dle these errors, refer to 12-1
How to Check for Errors.
Wait until the opening processing
is completed.
This error may occur if the CPU
Unit's task period was long when
opening the connection or some
problem in the Controller caused
the Controller to stop. If the task
period was too long, operation
recovers automatically. If the
Controller has stopped, identify
the error from the error informa-
tion in the CPU Unit.
This error may occur if the CPU
Unit's task period was long when
opening the connection. If the
task period was too long, opera-
tion recovers automatically.
Handling
Configuration 1
Depends on the originator's specifi-
cations. (Contact the originator
device's manufacturer.)
Depends on the originator's specifi-
cations. (Contact the originator
device's manufacturer.)
Depends on the originator's specifi-
cations. (Contact the originator
device's manufacturer.)
Depends on the originator's specifi-
cations. (Contact the originator
device's manufacturer.)
The meaning of this error code is
defined by each vendor, so it
depends on the originator's specifica-
tions. (Contact the originator device's
manufacturer.)
The meaning of this error code is
defined by each vendor, so it
depends on the originator's specifica-
tions. (Contact the originator device's
manufacturer.)
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Configuration 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx series

Table of Contents