Omron NXEIP202 User Manual page 151

Machine automation controller
Table of Contents

Advertisement

Terminal
Manufac-
types
Terminals
Weidmuller
other than
ground ter-
minals
*1. Some AWG14 wires exceed 2.0 mm
When you use any ferrules other than those in the above table, crimp them to the twisted wires so that
the following processed dimensions are achieved.
1.6 mm max.
(Terminals other than ground terminals)
2.0 mm max.
(Ground terminals)
 Using Twisted or Solid Wires
If you use twisted wires or solid wires, use the following table to determine the correct wire specifica-
tions.
Terminals
Classifica-
tion
All terminals
except
ground
terminals
Ground
terminals
*1. Secure wires to the screwless clamping terminal block. Refer to Securing Wires for how to secure wires.
*2. With the NX-TB1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a solid
wire.
Conductor length (stripping length)
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Applica-
ble wire
Ferrule
turer
model
(mm
(AWG))
H0.14/12
0.14 (#26)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
H0.5/16
H0.75/14
0.75 (#18)
H0.75/16
H1.0/14
1.0 (#18)
H1.0/16
H1.5/14
1.5 (#16)
H1.5/16
2
and cannot be used in the screwless clamping terminal block.
Twisted wires
Current
capacity
Plated
Unplated
2 A max.
Possible
Possible
Greater
Not pos-
than 2 A
sible
and 4 A
or less
Greater
*1
Possible
than 4 A
---
Possible
Possible
Crimping tool
2
Weidmuller (The figure in parentheses is the appli-
cable wire size.)
PZ6 Roto (0.14 to 6 mm
8 to 10mm
2.4 mm max.
(Terminals other than ground terminals)
2.7 mm max.
(Ground terminals)
Wire type
Solid wire
Plated
Unplated
Possible
Possible
*1
Not possi-
Possible
ble
Not possi-
ble
*2
*2
Possible
Possible
7 Wiring
2
, AWG26 to 10)
Conductor
length
Wire size
(stripping
length)
8 to 10 mm
2
0.08 to 1.5 mm
(AWG 28 to 16)
9 to 10 mm
2
2.0 mm
7 - 13
7