Omron NXEIP202 User Manual page 235

Machine automation controller
Table of Contents

Advertisement

Setting
Originator Variable
Connection Type
RPI
Timeout Value
2
After you make all of the settings, click the OK button.
Precautions for Correct Use
If you set a tag data link with a short packet interval (RPI) when many NX Units are connected
to the EtherNet/IP Slave Terminal, a Tag Data Link Timeout may occur depending on the load
conditions on the EtherNet/IP Slave Terminal. If that occurs, increase the length of the packet
interval (RPI) or reduce the number of NX Units that are mounted.
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Select and allocate the originator node's tag set.
• In: Select the originator's input (consume) tag set.
• Out: Select the originator's output (produce) tag set.
Select whether the data is sent in multi-cast or unicast (point-to-point) form.
The default setting is multi-cast.
• Multi-cast connection:
Select when the same data is shared by multiple nodes. This setting is usually
used.
• Point-to-point connection:
Select when the same data is not shared by
multiple nodes. In a unicast connection, other
nodes are not burdened with an unnecessary
load.
Note: Refer to 8-2-2 Creating Tag Data Links on page 8-7 for details on using
multi-cast and unicast connections.
Set the data update cycle (i.e., the packet interval) of each connection between
the originator and target.
• Minimum RPI for the EtherNet/IP Coupler Unit is 4 ms.
• The default setting is 50 ms (i.e., data is updated once every 50 ms).
• The interval can be set to an even number of ms (4, 6, 8,...)
• The interval can be set to between 4 and 1000 ms for the CJ2M-EIP21 and 0.5
and 10,000 ms for other CPU Units in 0.5-ms increments.
Set the time until a connection timeout is detected. The timeout value is set as a
multiple of the packet interval (RPI) and can be set to 4, 8, 16, 32, 64, 128, 256,
or 512 times the packet interval. The default setting is 4 times the packet interval
(RPI).
9 Setting Up Slave Terminals
Description
9
9 - 61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx series

Table of Contents