7.1.5

Completion status

No.
Completion name
1
Normal complete
2
Own station failure
3
Own station standby
4
Timeout
5
Length error
6
Station mode error
7
Own node parameter not set
8
Transmission prohibition
state
9
Format error
10
Transmission processed
11
Own station IP address error
12
LP→ OS information error
Table 7-16 Completion status list (Part 1)
Code
0 The request was completed normally.
-1 The request cannot be processed because the own station is in the
down mode.
-2 One of the following requests is issued in the standby mode:
(1) Common memory read request
(2) Common memory write request
(3) Message transmission request
-31 The written data was not transmitted for 2 seconds for a cyclic data
write request.
-47 (1) "Transmission data length" of the message transmission
request
(2) "Read word count" of the common memory read request
(3) "Write word count" of the common memory write request
-63 (1) Parameter setting was requested in other than the standby
mode.
(2) Standby was requested in other than the RUN mode.
(3) Run was requested in other than the standby mode.
-79 Run was requested without setting the own station parameter.
-95 A related request was issued from the controller while cyclic
transmission/message transmission was prohibited.
-111 (1)
The request text contained a format error.
(2)
A non-existing request type was used in an RAS
information read request.
-113 Request code error/non-existing request code was used.
-114 Time setting request: "Year" is invalid.
-115 Time setting request: "Month" is invalid.
-116 Time setting request: "Day" is invalid.
-117 Time setting request: "Hour" is invalid.
-118 Time setting request: "Minute" is invalid.
-119 Time setting request: "Second" is invalid.
-166 One of the following requests was returned for a message
transmission request:
(1) The request could not be processed because it is being
transmitted by other port.
(2) ACK was erroneous.
(3) The retransmission count was exceeded.
-161 An address other than Class C was specified for the IP address of
the FL911 for a parameter setting request.
-5100 Parameter error of XMIT_N FB (data length specification value)