(6) Make sure to perform insulation work for all drainage piping in order to prevent any possible
water drop due to dew condensation.
(7) Apply the suitable diameter for converging drainage pipe according to the operating capacity
of the unit.
(8) The horizontal pipe can't be connected to vertical pipe in the same level; please select the
connection way as shown in following figure.
1) Three-way connection of drainage pipe joints (Fig.4.3.3).
2) Connection of downspout elbow (Fig.4.3.4).
3) Inserting horizontal pipe connection (Fig.4.3.5).
Fig.4.3.3
(9) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes
from sagging, install hanger bracket at intervals of 1000~1500mm (39~3/8~59 inch).
(10) The installation height of raising pipe for drainage should be lower than B. The gradient from
Fig.4.3.2
Fig.4.3.4
Fig.4.3.6
10
Unit: mm (inch)
Fig.4.3.5
Unit: mm (inch)