High Static Fan Coil 220V/50-60Hz/1Ph Slim Fan Coil Low Static Fan Coil Large Fan Coil HS Thank you for selecting Air Handler Outside Air Thank you for selecting LENNOX air conditioners.Please read this manual carefully before operation and keep it for further reference.
Page 2
Preface For correct installation and operation, please read all instructions carefully. Before reading the instructions, please be aware of the following items: This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
(18) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please contact Lennox appointed service center for help. (19) Before installation, please check if the power supply is in accordance with the requirements specified on the nameplate.
Page 5
(26) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power supply, and then immerdiately contact Lennox appointed service center.If abnormality keeps going, the unit might be damaged and lead to electric shock or fire.
VEWCL1B Multi Variable Air Conditioners Cassette Type Indoor Unit 2 Product Introduction 2.1 Names of Key Components ① ② ③ ④ ⑤ ⑥ Name Air Outlet Filter Air Inlet Grille Fittings Louver Drainage Pipe 2.2 Rated Working Condition Indoor Side Condition Outdoor Side Condition Dry Bulb Temp (°F) Wet Bulb Temp (°F) Dry Bulb Temp...
Multi Variable Air Conditioners Cassette Type Indoor Unit 3 Preparations for Installation Note! this picture is for reference only, please refer to the actual product; the unit of dimension is inch. 3.1 Standard Fittings Use the following provided accessories according to the requirement. Name Appearance Q'ty...
Multi Variable Air Conditioners Cassette Type Indoor Unit 3.2 Installation Position Selection (1) The appliance shall not be installed in the laundry. (2) The location should be able to withstand the weight of unit. (3) The water can be drained conveniently from drainage pipe. (4) There should be no obstruction near air inlet and air outlet.
Multi Variable Air Conditioners Cassette Type Indoor Unit 3.3 Requirements of communication wire selection Note: If air conditioner used under strong electronic-magnetic interference circumstance, STP( shielded twisted pair) communication cable must be adopted. 3.3.1 Selection of communication wire between indoor unit and wired controller L(n-1) Sub-master Master...
Multi Variable Air Conditioners Cassette Type Indoor Unit Expansion bolt Fig 4.1.4 (2) Install the indoor unit temporarily Assemble suspension bolt on the expansion bolt, attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and washer from upper and lower sides of the hanger bracket. The washer fixing plate will prevent the washer from falling.
Multi Variable Air Conditioners Cassette Type Indoor Unit pipe joint of indoor unit flaring nut pipe joint Torque for tightening nut Pipe diameter Torque (N·m) mm(inch) 6.35(1/4) 15~30 9.52(3/8) 35~40 12.7(1/2) 45~50 wrench torque wrench 15.9(5/8) 60~65 Fig.4.2 (3) Use pipe bend when bending the pipe and the bending angle should not be too small. (4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape.
Page 14
Multi Variable Air Conditioners Cassette Type Indoor Unit water drop due to dew condensation. (7) Apply the suitable diameter for converging drainage pipe according to the operating capacity of the unit. Fig 4.3.2 drainage pipes assembled by T-shaped joints ① - (8) The installation height of raising pipe for drainage should be lower than 850mm(33-1/2 inch).
Multi Variable Air Conditioners Cassette Type Indoor Unit after running for 10min. (2) During the test, please carefully check the drainage joint, make sure no any leakage occur. (3) It’s strongly recommend to do the drain test before ceiling decoration. drainage pipe watering pot (the pipe should be about 100mm...
Page 16
Multi Variable Air Conditioners Cassette Type Indoor Unit indoor unit side panel side Fig 4.4.3 4.4.2 Panel installation (1) Detach the panel’s Corner Cap, there is a mark “piping side” on one of the 4 corners, adjust the panel direction so as to keep the mark and fittings on the same corner. (2) Temporality hang the panel to body (there is four hangers on each corner of the panel, hang the hangers to corresponding hooks on the body), as shown in fig 4.4.4.
Multi Variable Air Conditioners Cassette Type Indoor Unit 4.5 Wired controller installation Wired controller is optional accessory. If wired controller is needed, please contact your local dealer and install the wired controller according to the instruction manual. NOTICE! Do perform the commissioning operation before first use, automatic addressing or other settings, please refer to the manual of ODU.
Multi Variable Air Conditioners Cassette Type Indoor Unit 5 Wiring Work WARNING Before obtaining access to terminals, all supply circuits must be disconnected. NOTICE Units must be earthed securely, or it may cause electric shock. Please carefully read the wiring diagram before carry out the wiring work, incorrect wiring could cause malfunction or even damage the unit.
Multi Variable Air Conditioners Cassette Type Indoor Unit L1 L2 L1 L2 L1 L2 Fig 5.2 (1) For units with single-phase power supply. 1) Detach the electric box lid. 2) Let the power cord pass through the wiring through-holes. 3) Connect the power cord to terminal "L1, L2, ".
Multi Variable Air Conditioners Cassette Type Indoor Unit signal receiver (Standard) (Optional) Fig 5.4.1 Fig 5.4.2 2) Both IDU and wired controller are equipped with signal receiver, and available for wireless control respectively. (Optional) (Standard) Fig 5.4.3 5.5 Illuminate for Connection of Wired Controller and Indoor Units Network (1) Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1,D2.
Page 21
Multi Variable Air Conditioners Cassette Type Indoor Unit Fig 5.5...
Multi Variable Air Conditioners Cassette Type Indoor Unit 6 Routine Maintenance NOTICE (1) Do turn off the unit and cut off the main power supply when cleaning the air conditioner to avoid electric shock or injury. (2) Stand at solid table when cleaning the unit. (3) Do not clean the unit with hot water whose temperature is higher than 45°C to prevent fade or deformation.
Multi Variable Air Conditioners Cassette Type Indoor Unit 7 Table of Error Codes for Indoor Unit Error Error Error Content Content Content Code Code Code Quantity Of Group Control Water Temperature Sensor Indoor Unit Error Indoor Units Setting Error Error Indoor Units Incompatibility Indoor Fan Protection Jumper Cap Error...
Page 24