Toshiba MMK-AP0073HP1-E1 Service Manual page 81

Table of Contents

Advertisement

7-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
Check code
Main
Outdoor 7-segment display
remote
controller
Check code
Sub-code
E01
E02
E03
E04
E06
E06
No. of indoor units which
received signal normally
E07
E08
E08
Duplicated indoor
addresses
E09
Detected
AI-NET
Check code name
position
central control
remote controller
Remote
Communication error between
controller
indoor and remote controller
(Detected at remote controller side)
Remote
Remote controller sending error
controller
97
Indoor
Communication error between
unit
indoor and remote controller
(Detected at indoor side)
4
Indoor
Indoor/outdoor communication
unit
circuit error
(Detected at indoor side)
4
I/F
Decreased number of indoor units
I/F
Indoor/outdoor communication
circuit error
(Detected at outdoor side)
96
Indoor
Duplicated indoor addresses
I/F
99
Remote
Duplicated master remote
controller
controllers
Status
Error detection condition
Corresponding
Communication interrupted
unit only stops.
between indoor P .C. board and
remote controller.
Corresponding
Signal could not be sent from
unit only stops.
remote controller to indoor unit.
Corresponding
No communication from remote
unit only stops.
controller (including wireless) and
communication adaptor.
Corresponding
Indoor unit does not receive
unit only stops.
communication from outdoor unit.
All stop
When signal is not sent for a certain
period from the indoor unit which
has been used to send signals,
[E06] is normally displayed.
All stop
Transmission from outdoor to indoor
cannot continue for 30 seconds.
All stop
Multiple indoor unit address setup
are duplicated.
Corresponding
In 2-remote controller control
(including wireless), both are setup
unit only stops.
as master
(Header indoor unit stops and other
indoor unit is operating.)
Check item (position)
• Check remote controller inter-unit wire (A/B).
• Check disconnection, connector contact error.
• Check indoor power supply.
• Check indoor P .C. board error.
• Check remote controller address setup.
(When two remote controllers operate)
• Check remote controller P .C. board.
• Check the communication wire of remote controller:
Exchange remote controller.
• Check remote controller and communication
adaptor wiring.
• Check power-ON order of indoor/outdoor.
• Check indoor address setup.
• Check inter-unit wiring between indoor and outdoor.
• Check outdoor end terminal resistance setup
(SW30-2).
• Check SW02 setup on the wall type P .C. board.
(Should be Bit 1: ON, Bit 2: OFF)
• Check the power supply of indoor unit.
(Power-ON)
• Check connection of communication line between
indoor and outdoor.
• Check connector connection for communication in
indoor P .C. board.
• Check connector connection for communication in
outdoor P .C. board.
• Check indoor P .C. board failure.
• Check outdoor P .C. board (I/F) failure.
• Check outdoor end terminal resistance setup
(SW30-2).
• Check the communication connection between
indoor and outdoor.
• Check indoor address.
• Check the change of remote controller connection
(Group / individual) after setup of indoor address.
• Check SW02 setup on the wall type P .C. board.
(Should be Bit 1: ON, Bit 2: OFF)
• Check remote controller setup.
• Check remote controller P .C. board.

Advertisement

Table of Contents
loading

Table of Contents