Panasonic CS-HZ12RKE Service Manual page 77

Hide thumbs Also See for CS-HZ12RKE:
Table of Contents

Advertisement

15.3.3
Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown
below.
If the heat exchanger temperature exceeds 60°C, compressor will stop.
15.3.4
Compressor Oil Return Control
When compressor starts, the compressor will be regulated for 240 seconds.
15.3.5
Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
15.3.6
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor
and outdoor fan motor stop and the operation LED deice indicator ON during this operation.
OFF
60°C
Frequency Reduce
52°C
Frequency Limited
49°C
Free
Indoor Heat
Exchanger Temp.
77
46°C