Figure 29 - I/O Board Relay Contact Architecture - York YLUA0078 Installation Operation & Maintenance

Air-cooled scroll condensing units
Table of Contents

Advertisement

SECTION 9 – SERVICE AND TROUBLESHOOTING
Digital Outputs
Refer to the unit wiring diagram and Figure 29 on page
148. The digital outputs are located on TB7, TB8, and
TB9 and TB-10 of the microboard. ALL OUTPUTS
ARE 120 VAC with the exception of TB8-6 to TB8-7
which are the contacts that can be used for a remote
evaporator pump start signal. The voltage applied to
either of these terminals would be determined by field
wiring.
Each output is controlled by the microprocessor by
switching 120 VAC to the respective output connection
energizing contactors, evaporator heater, and solenoids
according to the operating sequence (see Figure 29 on
page 148).
120 VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1 and TB9-1
Figure 29 on page 148 illustrates the relay contact
architecture on the microboard.
148
TB7
TB7
TB10
TB10
TB8
FIGURE 29 - I/O BOARD RELAY CONTACT
ARCHITECTURE
FORM 150.73-NM1
ISSUE DATE: 09/04/2020
SYS 1
TB7-2
COMP 1
TB7-3
LLSV 1
SYS 1
TB7-4
COMP 2
SYS 1
TB7-5
COMP 3
SYS 1
TB7-7
HGSV
SYS 1
TB7-8
FAN 2
SYS 1
TB7-9
FAN 1
SYS 1
TB7-10
FAN 3
SYS 2
TB10-2
COMPR 1 (4)
TB10-3
LLSV 2
SYS 2
TB10-4
COMPR 2 (5)
SYS 2
TB10-5
COMPR 3 (6)
SYS 2
TB10-7
HGSV
TB10-8
SYS 2
TB10-9
FAN 2
SYS 2
TB10-10
FAN 4
TB8-6
EVAP
*
PUMP
TB8-7
HEAT EXCH
TB8-2
*
HEATER
* Not Used
LD12722
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ylua0158

Table of Contents