Status Key - York YLUA0078 Installation Operation & Maintenance

Air-cooled scroll condensing units
Table of Contents

Advertisement

FORM 150.73-NM1
ISSUE DATE: 09/04/2020
Unit Status
Pressing the STATUS key will enable the operator to
determine current unit operating status. The messages
displayed will include running status, cooling demand,
fault status, external cycling device status. The display
will be a single message relating to the highest priority
message as determined by the micro. Status messages
fall into the categories of General Status and Fault Sta-
tus.
The following General, Safety, and Warning messages
are displayed when the Status key is pressed. Follow-
ing each displayed message is an explanation pertain-
ing to that particular message.
General Status Messages
In the case of messages which apply to individual
systems, SYS 1 and SYS 2 messages will both be dis-
played and may be different. In the case of single sys-
tem units, all SYS 2 messages will be blank.
U N I T
S W I T C H
S H U T D O W N
This message informs the operator that the UNIT switch
on the control panel is in the OFF position which will
not allow the unit to run.
R E M O T E
C O N T R O L L E D
S H U T D O W N
The REMOTE CONTROLLED SHUTDOWN mes-
sage indicates that either an ISN system or RCC has
turned the unit "OFF", not allowing it to run.
D A I L Y
S C H E D U L E
S H U T D O W N
The DAILY SCHEDULE SHUTDOWN message in-
dicates that the daily/holiday schedule programmed is
keeping the unit from running.
JOHNSON CONTROLS

STATUS KEY

F L O W
NO RUN PERM shows that either the flow switch is
open or a remote start/stop contact is open in series
with the flow switch. A 3-second delay is built into the
software to prevent nuisance shutdowns due to errone-
ous signals on the run permissive input.
S Y S
S Y S
SYS SWITCH OFF tells that the system switch under
OPTIONS is turned "OFF". The system will not be al-
lowed to run until the switch is turned back on.
This message informs the operator that the discharge
air temperature is below the point (determined by the
setpoint and control range) that the micro will bring on
a system or that the micro has not loaded the lead sys-
O F F
tem far enough into the loading sequence to be ready to
bring the lag system "ON". The lag system will display
this message until the loading sequence is ready for the
lag system to start.
The COMPS RUNNING message indicates that the
respective system is running due to demand. The "X"
will be replaced with the number of compressors in
that system that are running.
These messages indicate that the zone thermostats
for system 1 and system 2 are open. These messages
will only be displayed when the control mode is pro-
grammed for Suction Pressure
SECTION 7 – UNIT CONTROLS
S W I T C H / R E M
N O
R U N
1
S Y S
S W I T C H
2
S Y S
S W I T C H
S Y S
1
N O
C O O L
S Y S
2
N O
C O O L
S Y S
1
C O M P S
S Y S
2
C O M P S
S Y S
1
Z O N E
S Y S
2
Z O N E
00066VIP
S T O P
P E R M
O F F
O F F
L O A D
L O A D
R U N
X
R U N
X
T H E R M
O F F
T H E R M
O F F
103
7