HOOKUP DIAGRAM

+
12 Volt 4 Ah
Gel-Cell
Battery Charge
Current is
360 mA Max
Battery capacity for
emergency standby is
at least 4 hours if the
total load (BELL & AUX
output) is 800mA or
less. Recommended
battery is Yuasa
MNP4-12.
16VAC
40 VA min.
50 to 60Hz AC
Do not connect transformer
to a receptacle controlled by
a switch.
Suggested Transformer:
Basler Electric
BE116240CAA-0002
PC1500RK
PC1500RKF
Keypad - 3 Max
Refer to the manual text
for detailed instructions
on keypad wiring.
For fire alarm applications, it is suggested that at least one indoor signalling appliance with a minimum 85dB rating and current rating
of 1 Amp or less be used (WHEELOCK model 34T-12-R rated 85dB(A) minimum for indoor residential applications).
Temperature Range: 0˚C to 47˚C (32˚F to 120˚F)
Maximum Humidity: 85% R.H.
Do not replace fuses with higher values than noted in this drawing.
Security detection devices that require power from control panel must operate over the voltage range of 10.0 to 14.0 VDC. The DSC
BRAVO series are recommended motion detectors.
pc15-cmd.cdr
JAN 7 1994
Pin 1
Pin 1
+
AUX +
AC
BELL
PGM
KEYPAD
YEL
SIREN
12 Volt DC
1 Amp
Max.
AUX
BLK
(+)
RED
YEL GRN
To
PGM
Smoke
Detector
Power
To
AUX
+
ULC-listed
latching 4-wire
smoke detector
(ESL model 446C)
EEPROM
Reset
Z1
COM
Z2
Z3
COM
Z4
GRN
NC
NO
End-of-Line
End-of-Line
Resistor
Resistor
1K 1/2W
1K 1/2W
EOL resistor
EOL resistor
loop using
loop using
NO & NC
NC devices
Devices
BLK
IN
-
-
N.O.
IN
OUT
ALM
+
+
OUT
WHT
RED
End of Line Resistor
1kΩ 1/2W
Z5
COM
Z6
R-1
T-1
RNG
TIP
GRY
BRN RED GRN
NC
RJ31-X cord
NC
RJ31-X
Telephone
Plug
only
WHT
RM-1 Power loop
supervisory relay
12VDC 35mA max.
GRN
Alarm initiating
loop resistance
100 ohms
Refer to installation guidelines
when placing smoke detectors.