Checking the sensors
External unit: NTC 50 k
1000
100
10
1
0.1
-30
-20
-10
0
Temperature in °C
Fig. 66
Checking fuses
Fuse location: See from page 33.
Fuse F1 is located on the mains terminal of the heat
pump control unit.
Fuse F3 is located on the main PCB.
Fuse F101 is located on the AVI PCB.
Fuses F1 and F3:
6.3 A (slow, H), 250 V~
Max. power loss
2.5 W
Danger
Removing the fuse does not switch the power
circuit to zero volt. Contact with 'live' compo-
nents can lead to serious injury from electric cur-
rent.
Before working on the equipment, always
ensure that the power circuit is also at zero
volt.
(cont.)
(without ID)
Ω
10
20
30
40
50
60
70
80
90
Fuse F101:
1.0 A (slow, L)
Max. power loss
2.5 W
Maintenance