Mitsubishi Electric PUMY-P112VKM4 Technical & Service Manual page 25

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM4:
Table of Contents

Advertisement

4-5. CORRECTING CAPACITY FOR CHANGES IN THE LENGTH OF REFRIGERANT PIPING
During cooling, obtain the ratio (and the equivalent piping length) of the outdoor units rated capacity and the total in-use
indoor capacity, and find the capacity ratio corresponding to the standard piping length from Figure 11 to 13. Then multiply
by the cooling capacity from Figure 7 and 8 in "4-2. CORRECTION BY TEMPERATURE" to obtain the actual capacity.
During heating, find the equivalent piping length, and find the capacity ratio corresponding to standard piping length from
Figure 14. Then multiply by the heating capacity from Figure 9 and 10 in "4-2. CORRECTION BY TEMPERATURE" to
obtain the actual capacity.
(1) Capacity Correction Curve
Figure 11
PUMY-P112VKM4(-BS)
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0
20
Figure 12
PUMY-P125VKM4(-BS)
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0
20
OCH673D
PUMY-P112YKM4(-BS)
40
60
80
Piping equivalent length (m)
PUMY-P125YKM4(-BS)
40
60
80
Piping equivalent length (m)
25
PUMY-P112YKME4(-BS)
Total capacity of indoor unit
100
120
140
PUMY-P125YKME4(-BS)
Total capacity of indoor unit
100
120
140
<Cooling>
6.3
9.4
12.5
16.2
160
180
<Cooling>
7.0
10.5
14.0
18.2
160
180