Mitsubishi Electric PUMY-P112VKM4 Technical & Service Manual page 101

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM4:
Table of Contents

Advertisement

Check code
6832
6833
,
(EF)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards
Continued from the previous page.
Refer to the chapter "Electrical
Work".
Is the wiring connected
properly, meeting the condition?
Yes
OCH673D
MA communication send error
Diagnosis
No
Connect the wiring properly as specified in
the chapter "Electrical Work" in the indoor
unit Installation Manual.
No abnormality
It might be caused by an external noise, so
check the transmission line to remove the
factor(s).
101
Chart 2 of 2
Remedy

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pumy-p125vkm4Pumy-p140vkm4Pumy-p112ykm4Pumy-p125ykm4Pumy-p140ykm4Pumy-p112ykme4 ... Show all

Table of Contents