Mitsubishi Electric PUMY-P112VKM4 Technical & Service Manual page 137

Split-type, heat pump air conditioners
Hide thumbs Also See for PUMY-P112VKM4:
Table of Contents

Advertisement

9-2-2. Cross section area of Wire for Main Power and ON/OFF capacities
<Outdoor unit> When power is supplied to outdoor unit and branch box separately
Model
P112–140VKM4
Outdoor Unit
P112–140YKM4
P112–140YKME4
<Outdoor unit> When power is supplied to branch box from the outdoor unit
Model
P112–140VKM4
Outdoor Unit
P112–140YKM4
P112–140YKME4
*1 A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2 In multi-phase appliance, the colour of the neutral conductor of the supply cord, if any, shall be blue.
<Indoor units> When power is supplied to indoor unit and outdoor unit separately
Total operating current of the indoor unit
4
F0 = 16 A or less *
4
F0 = 25 A or less *
4
F0 = 32 A or less *
Apply to IEC61000-3-3 about max. permissive system impedance.
3
*
The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
4
*
Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 16)/C}
Connect to Branch box (PAC-MK·BC)
Indoor unit
Type 1
PEAD-RP·JA(L)Q, PEAD-M·JA(L), PEY-(S)P·JA
SEZ-KD·VAQ(L), SEZ-M·DA(L), PCA-RP·KAQ, PCA-M·KA, PLA-RP·BA,
Type 2
PLA-RP·EA, SLZ-KF·VA2, SLZ-M·FA, PLY-(S)P·BA, SEZ-KH·VALT,
PCY-(S)P·KA, PLA-M·EA
Type 3
MLZ-KA·VA, MLZ-KP·VF
MFZ-KJ·VE2, MSXY-FJ·VE, MSZ-LN·VG, MSZ-AP·VG(D), MSZ-AP·VF,
Type 4
MSZ-EF·VG-E2, MSZ-EF·VGK-E1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
MSZ-FH·VE, MSZ-SF·VE, MSZ-EF·VE, MSZ-SF·VA, MSZ-GF·VE,
Type 5
MSZ-GE·VA, MSZ-EF·VA, MSY-GE·VA, MSY-EF·VA, MSZ-FH·VA,
MSY-GH·VA, MSZ-FK·VA, MSZ-GC·NA, MSZ-EF·VG-E1
Type 6
Branch box (PAC-MK·BC)
Type 7
ecodan (Cylinder unit, Hydrobox)
6
*
This value may increase due to a locally connected actuator.
Connect to Connection kit (PAC-LV11M-J)
Indoor unit
MFZ-KJ·VE2, MSZ-LN·VG, MSZ-AP·VG(D), MSZ-AP·VF, MSZ-EF·VG-E2,
Type 8
MSZ-EF·VGK-E1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
MSZ-GE·VA(D), MSZ-SF·VA, MSZ-SF·VE, MSZ-EF·VE, MSZ-FH·VE, MSY-
Type 9
GE·VA, MSY-GH·VA, MSZ-EF·VG-E1
Type 10 Connection kit (PAC-LV11M-J)
Connect to CITY MULTI
Indoor unit
Type 11 PEFY-P·VMA(L)-E(2), PEFY-P·VMA3-E
Type 12 PEFY-VMHS-E-F, PEFY-P10-140VMHS-E
PMFY-VBM-E, PLFY-VBM-E, PLFY-VEM-E, PLFY-VFM-E1,
PEFY-VMS1(L)-E, PCFY-VKM-E, PKFY-VHM-E, PKFY-VKM-E,
Type 13
PFFY-VKM-E2, PFFY-VLRMM-E, PLFY-EP·VEM-E, PMFY-P·VFM-D,
PKFY-VLM-E, PFFY-VCM-E
Type 14 PEFY-P·VMA(L)-E3, PEFY-M·VMA(L)-A
Type 15
Type 16 PLFY-VLMD-E, PEFY-VMR-E-L/R, PFFY-VLEM-E, PFFY-VLRM-E,
PWFY-VM-E1(2)-AU, PEFY-P·VMH-E-F, GUF-RD(H)4
C: Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
Condition PEFY-VMS × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*
5
Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + ···
+ V2 × (Quantity of Type16) + V3 × (Wire length[km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
OCH673D
Power Supply
Main Cable
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
2
3N~380-400-415 V, 50 Hz *
3N~380 V, 60 Hz
2
3N~380-400-415 V, 50 Hz *
Power Supply
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
2
3N~380-400-415 V 50 Hz *
3N~380 V, 60 Hz
2
3N~380-400-415 V 50 Hz *
Minimum wire thickness (mm²)
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
Wire thickness
137
Minimum Wire Cross-sec-
tional area (mm²)
Breaker for Wiring *
Ground
6
6
1.5
1.5
Minimum Wire Cross-sectional area
(mm²)
Breaker for Wiring *
Main Cable
Ground
6
6
2.5
2.5
Ground-fault interrupter *
Ground
1.5
20 A current sensitivity *
2.5
30 A current sensitivity *
4.0
40 A current sensitivity *
V1
V2
26.9
19.8
9.9
2.4
7.4
6.8
3.0
5.1
5.0 *
V1
V2
7.4
2.4
6.8
3.5
V1
V2
38.0
1.6
19.8
2.4
18.6
3.0
0.0
0.0
V3
2
1.5 mm
48
2
2.5 mm
56
2
4.0 mm
66
1
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 seconds or less
16 A
16 A 30 mA 0.1 seconds or less
1
Breaker for Current Leakage
40 A
40 A 30 mA 0.1 seconds or less
20 A
20 A 30 mA 0.1 seconds or less
Local switch (A)
Breaker for wiring
3
Capacity
Fuse
5
16
16
5
25
25
5
32
32
Sample chart
6000
600
60
10
1
6
0.1
0.01
1
2
3
4
Rated Tripping current (x)
Notes:
1. Bear in mind ambient conditions (ambi-
ent temperature, direct sunlight, rain
water, etc.) when proceeding with the
wiring and connections.
2. The wire size is the minimum value for
metal conduit wiring. The power cord
size should be 1 rank thicker considera-
tion of voltage drops.
Make sure the power-supply voltage
does not drop more than 10%.
3. Specific wiring requirements should
adhere to the wiring regulations of the
region.
4. Power supply cords of parts of appli-
ances for outdoor use shall not be lighter
than polychloroprene sheathed flexible
cord (design 60245 IEC57).
For example, use wiring such as YZW.
5. install an earth line longer than power
cables
Continue to the next page.
(NFB)
20
30
40
Sample
6
8
10
20
C