Download Print this page

Riello 40 F20 1/230/50 Installation, Use And Maintenance Instructions page 33

Light oil burners, one stage operation

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 27
4
AIR DAMPER ADJUSTMENT
The values stated in the table are necessary for the first setting of air-damper.
They are relevant to a burner with mounted cowling and combustion chamber with depression zero.
These values should be adjusted, on the basis of the specific requirements of the system, so that
the Bacharach number is not near 1.
ELECTRODES ADJUSTMENTS
Attention:
Before assembling or removing the noz-
zle, loosen the screw (A) and move the
electrodes ahead.
BURNER START-UP CYCLE
Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
WARNINGS TO AVOID BURNOUT OR BAD COMBUSTION OF THE BURNER
– When the burner is stopped, the smoke pipe must be opened and effect a natural draught in
the combustion chamber. If the smoke pipe is closed, the burner must be drawn back till the
extraction of blast tube from the furnace. Before operating in this way take the voltage off.
– The place, where the burner works, must have same openings suitable for the passage of air
necessary for combustion. To be sure about this, you have to control the smoke number of
exhaust gas with all the windows and doors closed.
– If in the place, where the burner works, there are air-breathings, check the existence of air-
input openings with dimensions suitable for the necessary air-exchange. In any case check
that, when the burner is stopped, the air-breathings do not draw warm smokes from pipes
through the burner.
2095
~
12s
4 ±
0.3 mm
D6313
A
Lock-out due to failure to light
~
12s
7
GB
MOVE
THE
ELEC-
TRODE HOLDER BACK-
WARDS TO THE END
6.5 ±
0.5 mm
~
5s
D5229

Advertisement

loading

This manual is also suitable for:

3452783