Viessmann Vitodens 200 Start-Up/Service Instructions page 56

Wall-mounted, gas-fired condensing boiler
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Additional Information
Control Unit for Weather-Responsive Operation
With standard progamming unit
Control unit setting:
Designs "04 02" and "04 03"
56
with programming unit
Adjusting heating curves (cont.)
Heating curve level
Designs "04:00" and "04:01":
Heating circuit without mixer
Designs "04:02" and "04:03":
Heating circuit with mixer
Differential temperature
Setting of coding address "07"
Differential temperature setting range from "07:00" = 6
K to "07:15" = 36 K (Change per step: 2 K)
As delivered condition: "07:01" = 8 K.
Note: If Vitotronic 050 is connected, the set differential
temperatures add up (as delivered condition
respectively 8 K). Therefore set the differential
temperature on Vitotronic 050 appropriately lower.
Maximum temperature limit
Heating circuit without mixer
Setting of coding address "06"
Setting range0 for max. temp. from "06:01" == 40ºC
to "06:15" == 110ºC (Change per step: 5 K)
As delivered 0condition: "06:10" == 85ºC.
Heating circuit with mixer
Setting of coding address "05"
Setting range0 for max. temp. from "05:00" == 35ºC
to "05:15" == 110ºC (Change per step: 5 K)
As delivered 0condition: "05:08" == 75ºC.
Vitodens 200 WB2 Service
(continued)