Specification for water/water heat pumps
Type BWC in conjunction with "conversion kit for water/
water heat pump"
Brine (primary intermediate circuit)
Capacity
Minimum flow rate
Residual head at minimum flow rate
Max. flow temperature (brine inlet)
Min. flow temperature (brine inlet)
Heating water (secondary circuit)
Capacity
Minimum flow rate
Residual head at minimum flow rate
Max. flow temperature
Note
Further specifications: See "Specification for brine/
water heat pumps".
(cont.)
301.C06
l
3.7
l/h
1220
mbar
750
kPa
75.0
°C
25
°C
7.5
l
4.5
l/h
490
mbar
720
kPa
72.0
°C
65
Specification
301.C12
301.C16
4.2
5.5
1520
1800
660
590
66.0
59.0
25
25
7.5
7.5
5.3
6.7
600
1100
705
650
70.5
65.0
65
65
85