Viessmann VITOCAL 300-G Installation And Service Instructions For Contractors page 26

Heat pump with electric drive
Table of Contents

Advertisement

Installation sequence
Electrical connection
Main PCB (function components 230 V~)
Information regarding the connection values
The specified output is the recommended connected
load.
Total output of all components connected directly to
the heat pump control unit (e.g. pumps, valves, mes-
sage facilities, contactors): Max. 1000 W
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the relevant relay must not
be exceeded.
The specified current indicates the max. switching
current of the switching contact. Observe total cur-
rent of 5 A.
Plug
sYA
Terminals
Function
211.1
Well pump
and/or
Additional primary pump to increase
residual head
Installation outside the heat pump
in the primary circuit flow
No switching via PWM signal from
the heat pump control unit
Note
The factory-fitted primary pump is
connected to the EEV PCB: See
chapter "Overview of electrical com-
ponents".
The factory-fitted primary pump
must be operated at a constant
100 % speed ("Start output pri-
mary source (htg) 7442" at
"100").
26
(cont.)
Set the required parameters during commissioning:
See page 51 onwards.
Explanation
Supply values
Output: 200 W
Voltage: 230 V~
Max. switching current: 4(2) A