Viessmann VITOCAL 300-G Installation And Service Instructions For Contractors page 16

Heat pump with electric drive
Table of Contents

Advertisement

Installation sequence
Siting the heat pump
Fitting the hydraulic connection set
The pipes of the primary circuit/secondary circuit
connection set are located in the EPP box, which is
positioned on top of the appliance on delivery.
With the primary circuit/secondary circuit connection
set, the on-site hydraulic lines can be connected at
the top of the heat pump.
Note
The following connection versions are possible with
the hydraulic connection sets available as accessories:
Connection of the primary lines to the right or left
Connection of all hydraulic lines at the back
Fitting the primary/secondary circuit connection set (standard delivery)
E
D
+
Fig. 8
Primary circuit flow (heat pump brine inlet), con-
A
nection Cu 28 x 1.5 mm
Primary circuit return (heat pump brine outlet),
B
connection Cu 28 x 1.5 mm
Secondary circuit flow (DHW cylinder), connection
C
Cu 28 x 1.5 mm
16
(cont.)
C
B
A
2.
5x
1.
5x
Note
We recommend fitting shut-off devices to the connec-
tion set on site. This will allow the primary and secon-
dary circuit to be shut off for maintenance work.
Secondary circuit flow (heating circuits), connec-
D
tion Cu 28 x 1.5 mm
Secondary circuit return (heating circuits DHW cyl-
E
inder), connection Cu 28 x 1.5 mm