Electrical connection
Plug
sYH
Terminals
Function
216.1
External hook-up, heating/cooling cir-
A1
cuits:
Central heating demand, heating cir-
cuit A1/HC1
Or
Smart Grid:
Floating contact 1
216.2
External hook-up, heating/cooling cir-
cuits:
Room cooling demand, heating circuit
A1
A1/HC1
216.4
Smart Grid:
Floating contact 2
Note
If external hook-up for heating/cooling circuits is con-
nected and selected, Smart Grid can be connected to
the EA1 extension (accessories) ("Enable Smart Grid
7E80" on "1").
Expansion PCB on main PCB (230 V~ components)
Information regarding the connection values
The specified output is the recommended connected
load.
Total output of all components connected directly to
the heat pump control unit (e.g. pumps, valves, mes-
sage facilities, contactors): Max. 1000 W
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the relevant relay must not
be exceeded.
The specified current indicates the max. switching
current of the switching contact. Observe total cur-
rent of 5 A.
(cont.)
Explanation
230 V~ digital input:
230 V~: Central heating demand for heating circuit
A1/HC1 active
0 V: No demand
Breaking capacity 230 V, 2 mA
230 V~ digital input:
230 V~: Contact active
0 V: Contact not active
Breaking capacity 230 V, 2 mA
230 V~ digital input:
230 V~: Room cooling demand for heating circuit
A1/HC1 active
0 V: No demand
Breaking capacity 230 V, 0.15 A
230 V~ digital input:
230 V~: Contact active
0 V: Contact not active
Breaking capacity 230 V, 2 mA
Set the required parameters during commissioning:
See page 51 onwards.
Installation sequence
29