Commissioning, inspection, maintenance
Commissioning the system
Setting parameters using "System scheme 7000"
as an example
To set a parameter, first select the parameter group
and then the parameter.
Service menu:
1. Press and hold OK +
approx. 4 s.
2. Select "Coding level 1".
3. Select parameter group: "System definition"
4. Select parameter: "System scheme 7000"
5. Set a system scheme: e.g. "6"
Required parameters for components connected on site
Parameters may need to be set subject to the appli-
ance type, the selected system scheme and the acces-
sories used.
Overview of required parameters: See the following
chapter.
System scheme
System schemes
Component
Heating circuit
A1/HC1
M2/HC2
M3/HC3
DHW cylinder
Immersion heater
Heating water buffer cylin-
der
External heat generator
Instantaneous heating water
heater
Swimming pool
Solar thermal system
Cooling
A1/HC1
M2/HC2
M3/HC3
Separate cooling circuit SKK
Only in conjunction with a heating water buffer cylinder.
*1
54
(cont.)
simultaneously for
å
System scheme
0
1
2
X
X
—
—
—
—
—
—
—
X
X
—
—
0
0
—
0
0
*1
*1
0
0
0
0
0
0
—
0
0
—
0
0
—
0
0
—
—
—
—
—
—
0
0
0
Alternatively, if the service menu was already active:
Extended menu:
1.
å
2. "Service"
3. Select "Coding level 1".
4. Select parameter group: "System definition"
5. Select parameter: "System scheme 7000"
6. Set a system scheme: e.g. "6"
Detailed explanations of parameters
"Vitotronic 200" service instructions
3
4
5
6
X
X
—
—
X
X
X
X
—
—
—
—
X
X
—
—
—
—
0
0
X
X
X
X
0
0
0
0
0
0
0
0
0
0
0
0
—
—
0
0
—
—
0
0
0
0
0
0
—
—
—
—
0
0
0
0
7
8
9
10
X
X
—
—
X
X
X
X
X
X
X
X
X
X
—
—
—
—
0
0
X
X
X
X
0
0
0
0
0
0
0
0
0
0
0
0
—
—
0
0
—
—
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
—
—
—
—
—
—
—
0
—
—
—
—
—
—