Rotating the terminal box depends on the mount and the cross-section of the internal stator
cables as well as the terminal box type:
● 1XB7730
● 1XB7731
● 1XB7740
● 1XB7750
Rotating a terminal box with mounted stator cables
1. Ensure that the motor is disconnected from the power supply.
2. Release two diagonally opposed screws for the cover, and secure the cover using two M10
3. If the motor is already connected:
4. Remove the grounding straps on two sides of the terminal box lower section.
5. Remove the screwed joints of the lower section with the console or optionally the cable duct.
6. Screw in two eye-bolts diagonally in the M10 thread at the corners. Slightly raise the terminal
7. Rotate the terminal box through ±90° in the desired direction. Carefully place the terminal
8. Screw the terminal box with the console / cable duct (4 x M16, tightening torque 170 Nm).
SIMOTICS FD 1MQ1
Operating Instructions 01/2019
– With installed internal stator cables, you can rotate the terminal box through ±90°.
– For six or fewer cables, you can rotate the terminal box with installed stator cables
through ±90°.
– For more than six cables, you must remove the internal stator cables before rotation.
– For 12 or fewer cables and lower cross-sections, you can rotate the terminal box with
installed stator cables through ±90°.
– For more than 12 cables - or for cables with a cross-section greater than 50 mm² - you
must remove the internal stator cables before rotating the terminal box.
– Remove the internal stator cables before rotating the terminal box.
threaded bars screwed in diagonally opposing one another. Release the two other screws
and lift the cover off the terminal box. The terminal box cover is very heavy. Especially when
in a lateral position, ensure that the terminal box does not fall down.
– Remove the cables of the power supply.
– Release the screw connection of the cable entry. Remove the cables through the
opening.
box housing using a crane.
box down. Take care not to damage the seal.
Electrical connection
6.3 Terminal box